{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2010-5HL36-0AD0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2010-5HL36-0AD0","canonicalUrl":"https://aoctrl.com/siemens/3VA2010-5HL36-0AD0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2010-5HL36-0AD0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2, molded case circuit breaker, 3-pole, 100 A continuous, adjustable thermal-magnetic trip 150–1200 A, breaking capacity 187 kA at 240 V AC, 86 mm depth, 105 mm width, 181 mm height.","salesMarkdown":"Its adjustable thermal-magnetic trip unit covers 150 A to 1200 A, so one frame size handles a wide range of downstream loads; set the trip to match your feeder or branch circuit, not the other way around. Breaking capacity is the headline selector: 187 kA at 240 V AC, 121 kA at 415/440 V, 75.6 kA at 500 V, and 3 kA at 690 V. The 690 V figure (3 kA) is low; if your system runs 690 V and fault current exceeds that, you need a higher-rated frame or a current-limiting upstream device. Power loss is 13.5 W maximum — negligible for thermal rise in a standard enclosure, but worth noting if you are packing multiple breakers into a sealed, non-ventilated cabinet. If you are comparing against the 3VA2116-5JP32-0AE0 (a higher-frame 160 A MCCB), note that the 3VA2010 is physically smaller — 105 mm wide vs the 3VA2116's wider footprint — so a direct swap without rewiring or re-drilling the mounting plate is not guaranteed. Always verify the mounting hole pattern and bus-bar spacing before committing. The breaker ships without a trip indicator, undervoltage release, communication module, or ground-fault monitoring — it is a bare line-protection device. If you need auxiliary contacts, the order code includes three auxiliary switches (HQ type). Verify that the auxiliary switch wiring matches your control voltage and that the switch rating covers your PLC input load.","metaTitle":"Siemens 3VA2010-5HL36-0AD0 SENTRON MCCB, 100 A, 3-Pole","metaDescription":"Siemens 3VA2010-5HL36-0AD0 SENTRON molded case circuit breaker, 100 A continuous, 3-pole, adjustable trip 150–1200 A, breaking capacity to 187 kA at 240 V. Active production. Quote","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"1 200 A","Minimum":"150 A","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"75.6 kA","at 690 V":"3 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"100 A","at 60 °C":"100 A","at 65 °C":"100 A","at 70 °C":"100 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"13.5 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA20105HL360AA0","Design Of The Auxiliary Switch":"3 auxiliary switches HQ","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"100 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU320","protection class IP / on the front":"IP40","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"100 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"3","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA12","Switching Capacity Class Of The Circuit Breaker":"M","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"double-sided box terminal","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=483882&mlfb=3VA2010-5HL36-0AD0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2010-5HL36-0AD0/alternatives.json"},"ai":{"faq":[{"question":"Will 3VA2010-5HL36-0AD0 drop into a panel specified for 3VA2116-5JP32-0AE0?","answer":"Not without checking the mounting footprint. The 3VA2010 is 105 mm wide; the 3VA2116 frame is wider. Bus-bar spacing and screw-hole positions differ — verify the mechanical interface before ordering."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2010-5HL36-0AD0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2010-5HL36-0AD0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}