{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2010-5HL36-0AE0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2010-5HL36-0AE0","canonicalUrl":"https://aoctrl.com/siemens/3VA2010-5HL36-0AE0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2010-5HL36-0AE0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2 series, molded case circuit breaker, 3-pole, 100 A rated continuous current (Iu), 187 kA breaking capacity at 240 V, ETU320 electronic trip unit, line protection version, IP40 front protection.","salesMarkdown":"This is a line protection version — no undervoltage release, no ground fault monitoring, no communication function. The 187 kA breaking capacity at 240 V (121 kA at 415 V, 79 kA at 500 V, 3.4 kA at 690 V) means it can safely interrupt very high fault currents without upstream cascading, making it suitable for main feeder positions or high-SCCR panels. The thermal derating curve matters for panel layout: at 40 °C it carries the full 100 A, but at 70 °C it derates to 85 A. The 105 mm width and 86 mm depth fit standard SENTRON 3VA2 panel cutouts; the 181 mm height is consistent across the family. Maximum power loss is 13.5 W, which is modest for a 100 A frame but still worth including in your enclosure thermal calculation. Mounts in a standard SENTRON panel cutout — no special adapter needed. The 4 HQ auxiliary switches (form C) are pre-installed; wire them before sliding the breaker onto the busbars. The ETU320 trip unit is field-replaceable if you later need a different curve. Front IP40 protection means it is splash-safe from the front but not sealed for washdown — keep it inside the enclosure.","metaTitle":"Siemens SENTRON 3VA2010-5HL36-0AE0 MCCB, 100 A, 187 kA","metaDescription":"Siemens SENTRON 3VA2010-5HL36-0AE0 molded case circuit breaker, 3-pole, 100 A rated continuous current, 187 kA breaking capacity at 240 V. ETU320 electronic trip unit. Current life","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"79 kA","at 690 V":"3.4 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"96.25 A","at 60 °C":"92.5 A","at 65 °C":"88.75 A","at 70 °C":"85 A","Trip indicator":"No","Number of poles":"3","Product version":"Line protection","Voltage trigger":"No","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"20 000","Undervoltage Release":"No","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"13.5 W","Auxiliary contact version":"4 auxiliary switches HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"100 A","Rated insulation voltage Ui":"800 V","Of The Supplied Basic Switch":"3VA2010-5HL36-0AA0","Design of the auxiliary release":"Without auxiliary release","Ground fault monitoring version":"Without","Design of the overcurrent release":"ETU320","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"17","Adjustable response value time / tr min.":"0.5","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"100 A","Adjustable response value current / li max.":"1 200 A","Adjustable response value current / li min.":"150 A","Adjustable response value current / lr min.":"40 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"4","Protective function of the overcurrent release":"LI","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA12","Switching capacity class of the circuit breaker":"M","Max. rated operational current of the frame size":"100 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"box terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, round conductor terminal, stranded":"1 x (6-120 mm²)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=439546&mlfb=3VA2010-5HL36-0AE0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2010-5HL36-0AE0/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for 3VA2010-5HL36-0AE0?","answer":"Submit an RFQ through this listing. Availability and current pricing are confirmed at quote time — no stock figures or lead-time numbers are published here."},{"question":"What is the closest functional second-source for 3VA2010-5HL36-0AE0?","answer":"The 3VA1010-2ED42-0AE0 is the nearest peer within the SENTRON 3VA family — same 100 A frame, 3 poles, and physical footprint. The key difference is the trip unit: the 3VA2010-5HL36-0AE0 uses an electronic ETU320, while the peer uses a thermal-magnetic unit. The 3VA2010 also carries 4 HQ auxiliary switches as standard."},{"question":"What are the physical dimensions of 3VA2010-5HL36-0AE0?","answer":"Depth is 86 mm, width is 105 mm, height is 181 mm. It fits standard SENTRON 3VA2 panel cutouts."},{"question":"Will 3VA2010-5HL36-0AE0 drop into a panel specified around 3VA1010-2ED42-0AE0?","answer":"Yes, the physical footprint (same frame size, 3-pole) is identical — it will mount in the same cutout and connect to the same busbars. The auxiliary contact wiring may differ because the 3VA2010-5HL36-0AE0 comes with 4 HQ switches versus the peer's standard complement."},{"question":"What compliance documentation is available for this MCCB?","answer":"The SENTRON 3VA series carries IEC/UL certifications typical for molded case circuit breakers. Specific RoHS, REACH, UL, and IEC declarations are available from the manufacturer upon request through the RFQ process."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2010-5HL36-0AE0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2010-5HL36-0AE0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}