{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2010-5HL36-0DA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2010-5HL36-0DA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2010-5HL36-0DA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2010-5HL36-0DA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2 molded case circuit breaker, 3VA2010-5HL36-0DA0, 3-pole, 100 A continuous rating, line protection design, with integrated undervoltage release (UVR).","salesMarkdown":"The Siemens 3VA2010-5HL36-0DA0 is a SENTRON 3VA2 molded case circuit breaker (MCCB) rated for 100 A continuous current, verified across the full operating temperature range from -25 °C to 70 °C with no derating — the 100 A holds at every 5 °C increment per the spec table. That means this breaker delivers its full nameplate rating in a warm panel without needing to oversize for ambient conditions. Breaking capacity is voltage-dependent: 187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 3 kA at 690 V.","metaTitle":"Siemens 3VA2010-5HL36-0DA0 SENTRON MCCB, 100 A, 3-Pole, UVR","metaDescription":"Siemens 3VA2010-5HL36-0DA0 SENTRON molded case circuit breaker, 100 A continuous, 3-pole, line protection, with undervoltage release. Breaking capacity 187 kA at 240 V. Current pro","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"1 200 A","Minimum":"150 A","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"75.6 kA","at 690 V":"3 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"100 A","at 60 °C":"100 A","at 65 °C":"100 A","at 70 °C":"100 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"Yes","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"16 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA20105HL360AA0","Design Of The Auxiliary Release":"undervoltage release (UVR)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"100 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU320","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9608-0BB25","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"100 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"M","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"double-sided box terminal","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=134028&mlfb=3VA2010-5HL36-0DA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2010-5HL36-0DA0/alternatives.json"},"ai":{"faq":[{"question":"What is the continuous current rating of this MCCB?","answer":"The continuous current rating is 100 A, and it holds that value across the entire operating temperature range from -25 °C to 70 °C with no derating required."},{"question":"Does this breaker include an undervoltage release?","answer":"Yes, the 3VA2010-5HL36-0DA0 includes an integrated undervoltage release (UVR) as the auxiliary release."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2010-5HL36-0DA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2010-5HL36-0DA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}