{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2010-5HL36-0DC0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2010-5HL36-0DC0","canonicalUrl":"https://aoctrl.com/siemens/3VA2010-5HL36-0DC0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2010-5HL36-0DC0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA series molded case circuit breaker, 3VA2010-5HL36-0DC0, 3-pole, 100 A, line protection, with undervoltage release and 2 auxiliary switches HQ.","salesMarkdown":"The Siemens SENTRON 3VA2010-5HL36-0DC0 is a 3-pole molded case circuit breaker rated for 100 A continuous current across the full 40 °C to 70 °C ambient range — no derating needed up to the enclosure's thermal limit. ## Breaking capacity — what the voltages tell you This MCCB delivers 187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 3 kA at 690 V. That steep drop above 500 V means the 690 V rating is essentially a switching-only figure — don't count on it for high-fault clearing at that voltage. For most 400 V-class industrial panels in North America (480Y/277 V) or Europe (400 V), the 121 kA figure gives solid headroom for high-capacity transformer feeds. ## Integrated auxiliaries and release Factory-fitted with two auxiliary switches (HQ type) and an undervoltage release (UVR). Power dissipation maxes out at 16 W, so in a sealed enclosure with multiple breakers side-by-side, factor that into the internal temperature rise calculation.","metaTitle":"Siemens 3VA2010-5HL36-0DC0 SENTRON MCCB, 100 A, 3-Pole, UVR","metaDescription":"Siemens SENTRON 3VA2010-5HL36-0DC0 molded case circuit breaker, 100 A continuous, 3-pole, line protection, undervoltage release. Breaking capacity 187 kA at 240 V. Current producti","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"1 200 A","Minimum":"150 A","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"75.6 kA","at 690 V":"3 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"100 A","at 60 °C":"100 A","at 65 °C":"100 A","at 70 °C":"100 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"Yes","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"16 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA20105HL360AA0","Design Of The Auxiliary Switch":"2 auxiliary switches HQ","Design Of The Auxiliary Release":"undervoltage release (UVR)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"100 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU320","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9608-0BB25","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"100 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"2","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA12","Switching Capacity Class Of The Circuit Breaker":"M","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"double-sided box terminal","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=148720&mlfb=3VA2010-5HL36-0DC0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2010-5HL36-0DC0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2010-5HL36-0DC0 and how do I get a price?","answer":"This part is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time."},{"question":"What is the breaking capacity of this MCCB at 240 V and 415 V?","answer":"Breaking capacity is 187 kA at 240 V and 121 kA at 415 V, providing ample fault-clearing capability for high-capacity transformer feeds in 400 V-class industrial panels."},{"question":"Does this breaker include an undervoltage release?","answer":"Yes, it is factory-fitted with an undervoltage release (UVR) that trips the breaker when control voltage drops, suitable for emergency-stop circuits or undervoltage protection."},{"question":"What compliance documentation is available for this SENTRON breaker?","answer":"As a Siemens SENTRON product, it carries standard certifications for industrial control panels; specific compliance documentation (RoHS, REACH, UL, IEC) is available upon request with the RFQ."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2010-5HL36-0DC0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2010-5HL36-0DC0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}