{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2010-5HL36-0HL0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2010-5HL36-0HL0","canonicalUrl":"https://aoctrl.com/siemens/3VA2010-5HL36-0HL0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2010-5HL36-0HL0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA, molded case circuit breaker, 3-pole, 100 A rated current, 187 kA at 240 V, line protection with ETU320 electronic trip unit, shunt trip release, 2 aux + 1 trip alarm + 1 electrical alarm switch.","salesMarkdown":"## What this MCCB delivers At 415 V the breaking capacity holds at 121 kA, dropping to 79 kA at 500 V and 3.4 kA at 690 V; that 690 V figure is the practical ceiling for this frame size in IEC applications. ## Trip unit and auxiliary complement Dimensions are 181 mm high, 105 mm wide, 86 mm deep, which fits standard SENTRON 3VA mounting footprints; verify busbar and lug clearance against the existing panel layout, especially the 86 mm depth behind the mounting plane.","metaTitle":"Siemens 3VA2010-5HL36-0HL0 SENTRON MCCB, 100 A, 187 kA at 24","metaDescription":"Siemens SENTRON 3VA2010-5HL36-0HL0 molded case circuit breaker, 3-pole, 100 A, 187 kA breaking capacity at 240 VAC. Line protection with ETU320 release. Quoted to order against RFQ","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"79 kA","at 690 V":"3.4 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"96.25 A","at 60 °C":"92.5 A","at 65 °C":"88.75 A","at 70 °C":"85 A","Trip indicator":"Yes","Number of poles":"3","Product version":"Line protection","Voltage trigger":"Yes","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"20 000","Undervoltage Release":"No","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"13.5 W","Auxiliary contact version":"2 auxiliary switches + 1 trip alarm switch + 1 electrical alarm switch HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"100 A","Rated insulation voltage Ui":"800 V","Of The Supplied Basic Switch":"3VA2010-5HL36-0AA0","Design of the auxiliary release":"Shunt trip (STL)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9688-0BL30","Design of the overcurrent release":"ETU320","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"17","Adjustable response value time / tr min.":"0.5","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"100 A","Adjustable response value current / li max.":"1 200 A","Adjustable response value current / li min.":"150 A","Adjustable response value current / lr min.":"40 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"4","Protective function of the overcurrent release":"LI","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB22","Switching capacity class of the circuit breaker":"M","Max. rated operational current of the frame size":"100 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"box terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, round conductor terminal, stranded":"1 x (6-120 mm²)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=316636&mlfb=3VA2010-5HL36-0HL0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2010-5HL36-0HL0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2010-5HL36-0HL0 and what is the price?","answer":"This MCCB is sourced and quoted to order against an RFQ through independent distribution. Current pricing and availability are confirmed at quote time — no stock count or price figure is published here."},{"question":"What is the breaking capacity of 3VA2010-5HL36-0HL0 at different voltages?","answer":"At 240 V the interrupting rating is 187 kA; at 415 V and 440 V it is 121 kA; at 500 V it drops to 79 kA; and at 690 V the rating is 3.4 kA. These figures govern where the breaker can be applied in high-fault panels."},{"question":"What auxiliary switches come with this MCCB?","answer":"The factory-fitted auxiliary contact block includes two auxiliary switches, one trip-alarm switch, and one electrical-alarm switch — four discrete signals for status monitoring."},{"question":"Does 3VA2010-5HL36-0HL0 include a shunt trip release?","answer":"Yes, it is equipped with a shunt trip (STL) release for remote tripping via a control voltage. No undervoltage release is fitted."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2010-5HL36-0HL0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2010-5HL36-0HL0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}