{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2010-5HL36-0KF0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2010-5HL36-0KF0","canonicalUrl":"https://aoctrl.com/siemens/3VA2010-5HL36-0KF0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2010-5HL36-0KF0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens 3VA2 IEC frame 100, breaking capacity class M, Icu=55kA @ 415V, 3-pole, line protection ETU320, LI, In=100A, overload Ir=40A...100A, short-circuit Ii=1.5...12 x In, clamp connection, shunt trip (STL) 220-250V DC / 208-277V AC, 1 auxiliary switch HQ, 1 trip alarm switch HQ.","salesMarkdown":"The continuous current rating In is 100 A, with overload protection (Ir) adjustable from 40 A to 100 A and short-circuit protection (Ii) adjustable from 1.5 to 12 times In. That means one breaker covers a wide band of feeder or branch-circuit sizes without swapping the frame. ## Integrated accessories That covers remote tripping and status feedback without adding separate modules. Termination is clamp (box lug) type — no special crimp tooling needed for the panel builder, and it accepts a solid or stranded conductor range typical for 100 A feeders.","metaTitle":"Siemens 3VA2010-5HL36-0KF0 Circuit Breaker, 55kA @ 415V, 100","metaDescription":"Siemens 3VA2010-5HL36-0KF0 IEC frame 100 breaker, 55kA @ 415V, 3-pole, ETU320 LI, In=100A, Ir=40-100A, Ii=1.5-12xIn. Current lifecycle stage. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"lifecycle_stage":"current"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=906600&mlfb=3VA2010-5HL36-0KF0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2010-5HL36-0KF0/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of this breaker?","answer":"The 3VA2010-5HL36-0KF0 has an Icu of 55 kA at 415 V AC, which is breaking capacity class M per the IEC frame 100 rating."},{"question":"What are the adjustable protection settings on this ETU320 trip unit?","answer":"Overload protection Ir is adjustable from 40 A to 100 A, and short-circuit protection Ii is adjustable from 1.5 to 12 times In (In = 100 A)."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2010-5HL36-0KF0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2010-5HL36-0KF0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}