{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2010-5HN32-0KH0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2010-5HN32-0KH0","canonicalUrl":"https://aoctrl.com/siemens/3VA2010-5HN32-0KH0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2010-5HN32-0KH0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2010-5HN32-0KH0, 3-pole molded case circuit breaker, 100 A continuous, 187 kA interrupting at 240 V, line protection with shunt trip and auxiliary switches.","salesMarkdown":"The 3-pole frame handles three-phase circuits up to 690 V, with interrupting ratings that step down from 187 kA at 240 V to 121 kA at 415/440 V, 75.6 kA at 500 V, and 3 kA at 690 V. The undervoltage release is not present on this variant. The trip indicator and voltage trigger are built in. Mounting is screw-clamp to the DIN rail or direct panel mount via the breaker's base. Max power loss is 13.5 W — negligible for enclosure thermal calculations but worth noting if you're packing multiple breakers in a small box.","metaTitle":"Siemens 3VA2010-5HN32-0KH0 SENTRON MCCB, 100 A, 3-Pole, 187","metaDescription":"Siemens SENTRON 3VA2010-5HN32-0KH0 molded case circuit breaker, 100 A continuous, 3-pole, 187 kA at 240 V. Line protection with shunt trip. Current lifecycle; sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"1 200 A","Minimum":"1 200 A","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"75.6 kA","at 690 V":"3 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"100 A","at 60 °C":"100 A","at 65 °C":"100 A","at 70 °C":"100 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"Yes","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"13.5 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA20105HN320AA0","Design Of The Auxiliary Switch":"2 auxiliary switches + 1 trip alarm switch HQ","Design Of The Auxiliary Release":"shunt trip (STL)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"100 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU350","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9688-0BL33","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"100 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"3","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB12","Switching Capacity Class Of The Circuit Breaker":"M","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=323529&mlfb=3VA2010-5HN32-0KH0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2010-5HN32-0KH0/alternatives.json"},"ai":{"faq":[{"question":"What is 3VA2010-5HN32-0KH0's listed depth (86 mm) on this component line?","answer":"The depth is 86 mm (3.39 in). That is the dimension from the mounting plane to the front of the breaker body, not including the handle throw."},{"question":"What compliance documentation does this brand provide for 3VA2010-5HN32-0KH0 (RoHS, REACH, UL, IEC)?","answer":"Standard SENTRON-series compliance documentation is provided with the shipment, covering RoHS, REACH, UL, and IEC certifications. Specific declarations are available on request at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2010-5HN32-0KH0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2010-5HN32-0KH0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}