{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2010-5HN36-0JC0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2010-5HN36-0JC0","canonicalUrl":"https://aoctrl.com/siemens/3VA2010-5HN36-0JC0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2010-5HN36-0JC0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON molded case circuit breaker, 3VA2010-5HN36-0JC0, 3-pole, 100 A, 187 kA at 240 V, line protection with shunt trip.","salesMarkdown":"The Siemens SENTRON 3VA2010-5HN36-0JC0 is a 3-pole molded case circuit breaker rated for 100 A continuous current across the full operating temperature range from -25 °C to 70 °C — no derating needed up to 70 °C, which is a solid feature for a warm panel. It carries a massive 187 kA interrupting capacity at 240 V, dropping to 121 kA at 415/440 V, 75.6 kA at 500 V, and 3 kA at 690 V. That kind of short-circuit rating means it can sit upstream of a high-fault transformer or a big motor control center and still clear a dead short without welding its contacts shut. A 100 A frame with 187 kA SCCR at 240 V is unusual — most 100 A MCCBs top out around 65-100 kA. This one is sized for high-fault locations like the service entrance of a large industrial plant or a substation feeder. The 3-pole design handles three-phase loads up to 100 A continuous. Two HQ auxiliary switches give you status feedback for the PLC or annunciator panel. ## Panel integration The shunt trip and auxiliary switches are factory-installed — no field-assembly required.","metaTitle":"Siemens 3VA2010-5HN36-0JC0 SENTRON MCCB, 100 A, 3-Pole, 187","metaDescription":"Siemens 3VA2010-5HN36-0JC0 SENTRON molded case circuit breaker, 100 A continuous, 3-pole, 187 kA at 240 V. Active production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"1 200 A","Minimum":"1 200 A","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"75.6 kA","at 690 V":"3 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"100 A","at 60 °C":"100 A","at 65 °C":"100 A","at 70 °C":"100 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"Yes","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"13.5 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA20105HN360AA0","Design Of The Auxiliary Switch":"2 auxiliary switches HQ","Design Of The Auxiliary Release":"shunt trip (STL)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"100 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU350","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9688-0BL32","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"100 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"2","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA12","Switching Capacity Class Of The Circuit Breaker":"M","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"double-sided box terminal","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=282413&mlfb=3VA2010-5HN36-0JC0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2010-5HN36-0JC0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2010-5HN36-0JC0 and how do I get a price?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time."},{"question":"What is the interrupting capacity of 3VA2010-5HN36-0JC0 at 240 V?","answer":"It is rated for 187 kA at 240 V, dropping to 121 kA at 415/440 V, 75.6 kA at 500 V, and 3 kA at 690 V."},{"question":"What compliance documentation does this brand provide for 3VA2010-5HN36-0JC0?","answer":"Siemens SENTRON breakers typically carry UL, CSA, CE, and IEC certifications, plus RoHS and REACH compliance. The specific approvals for this order code should be verified against the nameplate or the manufacturer's declaration at order time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2010-5HN36-0JC0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2010-5HN36-0JC0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}