{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2010-5HN36-0JH0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2010-5HN36-0JH0","canonicalUrl":"https://aoctrl.com/siemens/3VA2010-5HN36-0JH0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2010-5HN36-0JH0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2010-5HN36-0JH0, molded case circuit breaker, 100 A continuous, 3-pole, 187 kA interrupting at 240 V AC, line protection design, with shunt trip and auxiliary switches.","salesMarkdown":"The Siemens SENTRON 3VA2010-5HN36-0JH0 is a 3-pole molded case circuit breaker rated 100 A continuous across the full ambient range from 40 °C to 70 °C — no derating needed up to that ceiling. Interrupting capacity hits 187 kA at 240 V AC, dropping to 121 kA at 415 V and 440 V, then 75.6 kA at 500 V, and 3 kA at 690 V. That's a lot of fault-clearing headroom for a 100 A frame; it's sized for high-available-fault-current panels where a standard 65 kA MCCB would be marginal. The 105 mm width (4.13 in) is the 3-pole frame width; verify against existing busbar or finger-safety shrouds if retrofitting into a live panel. ## Auxiliary wiring and shunt trip note The shunt trip (STL) lets you remotely open the breaker from a PLC dry contact or emergency-stop circuit — verify the release coil voltage matches your control supply (the order code doesn't encode coil voltage; it's a separate ordering step). The two auxiliary switches plus trip alarm switch give you three discrete status signals: breaker open/closed, and a separate alarm contact that changes state only on a fault trip. Useful for SCADA feedback without adding an external interposing relay.","metaTitle":"3VA2010-5HN36-0JH0 SENTRON MCCB, 100A, 3-Pole, 187kA at 240V","metaDescription":"SENTRON 3VA2010-5HN36-0JH0 molded case circuit breaker, 100A continuous, 3-pole, 187kA interrupting at 240V AC. Active production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"1 200 A","Minimum":"1 200 A","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"75.6 kA","at 690 V":"3 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"100 A","at 60 °C":"100 A","at 65 °C":"100 A","at 70 °C":"100 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"Yes","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"13.5 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA20105HN360AA0","Design Of The Auxiliary Switch":"2 auxiliary switches + 1 trip alarm switch HQ","Design Of The Auxiliary Release":"shunt trip (STL)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"100 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU350","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9688-0BL32","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"100 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"3","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB12","Switching Capacity Class Of The Circuit Breaker":"M","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"double-sided box terminal","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=29214&mlfb=3VA2010-5HN36-0JH0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2010-5HN36-0JH0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2010-5HN36-0JH0 and what is the lead time?","answer":"This part is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm lead time and price."},{"question":"What are the key ratings for 3VA2010-5HN36-0JH0?","answer":"100 A continuous at 40–70 °C ambient, 3-pole, 187 kA interrupting at 240 V AC, 121 kA at 415 V, 75.6 kA at 500 V, 3 kA at 690 V. Power loss 13.5 W max."},{"question":"Does 3VA2010-5HN36-0JH0 include a shunt trip and auxiliary switches?","answer":"Yes, it comes with a shunt trip (STL) release and two auxiliary switches plus one trip alarm switch HQ — remote open capability and three status signals built in."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2010-5HN36-0JH0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2010-5HN36-0JH0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}