{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2010-5JP32-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2010-5JP32-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2010-5JP32-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2010-5JP32-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA series, molded case circuit breaker, 3VA2010-5JP32-0AA0, 100 A, 3-pole, ETU550 electronic trip unit, 187 kA at 240 V.","salesMarkdown":"The 187 kA interrupting rating at 240 V (121 kA at 415/440 V, 75.6 kA at 500 V, and still 3 kA at 690 V) means it handles high fault currents on the secondary side of a transformer or in a 480 V MCC lineup without needing a current-limiting fuse ahead of it. It's a current-production part, still in the catalog as an active line item. That's unusual for a compact frame; most MCCBs start dropping current above 40 °C. The 86 mm depth and 105 mm width (3.39 by 4.13 inches) fit standard Siemens 3VA mounting bases, so if you're swapping into an existing SENTRON panelboard or a 3VA-based MCC bucket, the footprint matches without buswork rework. The ETU550 release communicates (communication function is built in), so you can pull trip data and event logs over the bus without adding an external module.","metaTitle":"Siemens SENTRON 3VA2010-5JP32-0AA0 MCCB, 100 A, 3-Pole, ETU5","metaDescription":"Siemens SENTRON 3VA2010-5JP32-0AA0 molded case circuit breaker, 100 A continuous, 3-pole, ETU550 release, 187 kA at 240 V. Active production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"1 200 A","Minimum":"150 A","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"75.6 kA","at 690 V":"3 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"100 A","at 60 °C":"100 A","at 65 °C":"100 A","at 70 °C":"100 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"13.5 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"100 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU550","protection class IP / on the front":"IP40","design of the N-conductor protection":"adjustable OFF; 20% to 160%","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"100 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"M","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/abf726200ead53da2aba675e713d960f.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=348686&mlfb=3VA2010-5JP32-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2010-5JP32-0AA0/alternatives.json"},"ai":{"faq":[{"question":"Will 3VA2010-5JP32-0AA0 drop into a panel built for 3VA2010-5HL36-0BE0?","answer":"Both are 3-pole 100 A SENTRON 3VA frame breakers with the same physical footprint (86 mm deep, 105 mm wide, 181 mm tall), so they share the same mounting base and bus connections. The main difference is the trip unit — the 5JP32 carries an ETU550 electronic trip with communication, while the 5HL36 uses a different release. No rewiring needed for the power circuit, but verify the control wiring if you're using the communication function."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2010-5JP32-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2010-5JP32-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}