{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2010-5JP36-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2010-5JP36-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2010-5JP36-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2010-5JP36-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2010-5JP36-0AA0, molded case circuit breaker, 3-pole, 100 A continuous, interrupting capacity 187 kA at 240 V, line protection version with ETU550 electronic trip unit.","salesMarkdown":"The Siemens SENTRON 3VA2010-5JP36-0AA0 is a 3-pole molded case circuit breaker (MCCB) rated for 100 A continuous current across the full ambient range from 40 °C to 70 °C, with no derating required up to the maximum operating temperature. Its interrupting capacity is 187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 3 kA at 690 V — figures that define the available fault current it can safely clear at each voltage level without upstream coordination failure. Front face protection is IP40, suitable for enclosed panel installations where tools are required to access the breaker; the optional motor drive extension (listed as available) allows remote tripping or reset without opening the door. ## Electrical ratings and application context","metaTitle":"Siemens 3VA2010-5JP36-0AA0 SENTRON MCCB, 100 A, 3-Pole, 187","metaDescription":"Siemens SENTRON 3VA2010-5JP36-0AA0 molded case circuit breaker, 100 A continuous, 3-pole, 187 kA interrupting at 240 V. Line protection version with ETU550 release. Current lifecyc","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"75.6 kA","at 690 V":"3 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"100 A","at 60 °C":"100 A","at 65 °C":"100 A","at 70 °C":"100 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"No","Number Of Poles":"3","Product version":"Line protection","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Communication Function":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"13.5 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Courant permanent assigné Iu":"100 A","Ground-Fault Monitoring Version":"Without","Tension assignée d'isolement Ui":"800 V","Design Of The Overcurrent Release":"ETU550","protection class IP / on the front":"IP40","reference code / acc. to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"Yes","Adjustable response value current / li max.":"1 200 A","Adjustable response value current / li min.":"150 A","Neutral conductors / upgradeable/retrofittable":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"M","Max. rated operational current of the frame size":"100 A","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"double-sided box terminal","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal","Type of connectable conductor cross-section, round conductor terminal, stranded":"1 x (6-120 mm²)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/f84737e24aa6139192e48cff5a1945f6.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=409126&mlfb=3VA2010-5JP36-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2010-5JP36-0AA0/alternatives.json"},"ai":{"faq":[{"question":"Will 3VA2010-5JP36-0AA0 drop into a panel specified for 3VA2010-8HL42-0AA0?","answer":"Both breakers share the same 3VA2 frame dimensions (105 mm wide, 181 mm high, 86 mm deep), so the physical footprint is identical and no rewiring of the bus or mounting is required. The difference is in the trip unit and accessories — verify the ETU550 release and communication function match your coordination study before swapping."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2010-5JP36-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2010-5JP36-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}