{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2010-5JQ32-0DL0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2010-5JQ32-0DL0","canonicalUrl":"https://aoctrl.com/siemens/3VA2010-5JQ32-0DL0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2010-5JQ32-0DL0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2010-5JQ32-0DL0, molded case circuit breaker, 3-pole, 100 A rated current, line protection design, with communication function and undervoltage release.","salesMarkdown":"Three poles, so it handles three-phase loads without needing a fourth pole for the neutral. Breaking capacity is where this breaker earns its keep: 187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and still 3 kA at 690 V. That's a high-interrupting rating for a 100 A frame — it'll clear a bolted fault upstream without the arc flash climbing into the next panel. ## What the auxiliary package means for panel wiring Includes two auxiliary switches, one trip alarm switch, one electrical alarm switch (HQ), and an undervoltage release. Communication function is present on this variant. It can interface with a higher-level system via the SENTRON communication module. ## Temperature performance and storage limits Storage range is wider: -40 °C to 80 °C, which covers most warehouse and shipping conditions. No special cold-weather start-up sequence needed — the breaker is ready at -25 °C.","metaTitle":"Siemens 3VA2010-5JQ32-0DL0 SENTRON MCCB, 100 A, 3-Pole, Line","metaDescription":"Siemens SENTRON 3VA2010-5JQ32-0DL0 molded case circuit breaker, 100 A rated at 40 °C, 3-pole, 187 kA at 240 V. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"1 200 A","Minimum":"150 A","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"75.6 kA","at 690 V":"3 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"100 A","at 60 °C":"100 A","at 65 °C":"100 A","at 70 °C":"100 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Initial Value":"20 A","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Full-Scale Value":"100 A","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"Yes","Design Of The Product":"Line protection","Communication Function":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"16 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA20105JQ320AA0","Design Of The Auxiliary Switch":"2 auxiliary switches + 1 trip alarm switch + 1 electrical alarm switch HQ","Design Of The Auxiliary Release":"undervoltage release (UVR)","Ground-Fault Monitoring Version":"Summation current formation L-conductor","Continuous Current / Rated Value":"100 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU560","protection class IP / on the front":"IP40","design of the N-conductor protection":"adjustable OFF; 20% to 160%","Of The Integrated Auxiliary Trip Unit":"3VA9608-0BB25","Product Function / Grounding Protection":"Yes","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"100 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSIG","number of CO contacts / for auxiliary contacts":"4","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB22","Switching Capacity Class Of The Circuit Breaker":"M","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=451063&mlfb=3VA2010-5JQ32-0DL0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2010-5JQ32-0DL0/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2010-5JQ32-0DL0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2010-5JQ32-0DL0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}