{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2010-5JQ42-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2010-5JQ42-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2010-5JQ42-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2010-5JQ42-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2010-5JQ42-0AA0, 4-pole molded case circuit breaker, 100 A, ETU560 electronic trip unit, 187 kA at 240 V AC, line protection.","salesMarkdown":"The Siemens 3VA2010-5JQ42-0AA0 is a 4-pole SENTRON molded case circuit breaker rated for 100 A continuous current across the full 40 °C to 70 °C ambient range — no derating needed up to 70 °C, which simplifies panel layout in warm enclosures or near other heat sources. Its ETU560 electronic trip unit enables adjustable N-conductor protection (OFF, 20% to 100%) and ground-fault monitoring via summation current formation on L + N — critical for selective coordination on 4-wire systems where neutral protection must match the phase breaker setting. Breaking capacity ranges from 187 kA at 240 V AC down to 3 kA at 690 V AC; at 415 V and 440 V it holds 121 kA, giving headroom for high-fault installations like industrial substations or large motor control centers. Dimensions of 86 mm depth, 140 mm width, and 181 mm height fit standard 4-pole MCCB panel cutouts — verify gland plate clearance for the 86 mm depth, especially in shallow enclosures. Maximum power loss 13.5 W; operating temperature range -25 °C to 70 °C, storage -40 °C to 80 °C. Communication function integrated.","metaTitle":"Siemens 3VA2010-5JQ42-0AA0 SENTRON MCCB, 100 A, 4-Pole, ETU5","metaDescription":"Siemens 3VA2010-5JQ42-0AA0 SENTRON MCCB, 100 A continuous at 40-70 °C, 4-pole, ETU560 electronic release, 187 kA at 240 V AC. Active production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"140 mm","Height":"181 mm","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"75.6 kA","at 690 V":"3 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"100 A","at 60 °C":"100 A","at 65 °C":"100 A","at 70 °C":"100 A","Depth [In]":"3.39 in","Width [In]":"5.51 in","Height [In]":"7.13 in","Trip Indicator":"No","Number Of Poles":"4","Product version":"Line protection","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Communication Function":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"13.5 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Courant permanent assigné Iu":"100 A","Ground-Fault Monitoring Version":"Summation current formation L + N conductor","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU560","protection class IP / on the front":"IP40","design of the N-conductor protection":"adjustable OFF; 20% to 100%","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"100 A","Product Extension / Optional / Motor Drive":"Yes","Adjustable response value current / lg max.":"100 A","Adjustable response value current / lg min.":"20 A","Neutral conductors / upgradeable/retrofittable":"No","Protection Function Of The Overcurrent Release":"LSIG","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"M","Mechanical Service Life (Switching Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"25 x 8 mm","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"13 x 1 mm"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/405e063f3e682cface3c1edfc839c7c8.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=260904&mlfb=3VA2010-5JQ42-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2010-5JQ42-0AA0/alternatives.json"},"ai":{"faq":[{"question":"What is 3VA2010-5JQ42-0AA0's listed depth?","answer":"86 mm — check gland plate clearance in shallow enclosures before ordering."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2010-5JQ42-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2010-5JQ42-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}