{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2010-5KP32-0HA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2010-5KP32-0HA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2010-5KP32-0HA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2010-5KP32-0HA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2010-5KP32-0HA0, molded case circuit breaker, 3-pole, 100 A rated continuous current Iu, 187 kA interrupting at 240 V, ETU850 electronic trip unit, shunt trip release, communication function.","salesMarkdown":"Its 100 A continuous current at 40 °C holds steady through 50 °C before derating begins — at 55 °C it carries 96.25 A, at 70 °C it still handles 85 A. The interrupting ratings are the headline: 187 kA at 240 V, 121 kA at 415 V and 440 V, 79 kA at 500 V, and 3.4 kA at 690 V. It also includes a communication function for remote monitoring and trip indication — useful for a plant-floor SCADA tie-in. No last-time-buy window is announced. No auxiliary contacts are factory-fitted; if you need them, they mount externally on the left side. Maximum power loss is 13.5 W. The closest functional peer is the 3VA1110-5EE32-0JA0. Both are 3-pole SENTRON MCCBs with electronic trip units. The key difference: the 3VA1110 frame is physically smaller (76 mm wide vs 105 mm) and has a lower interrupting rating — typically 65 kA at 240 V versus 187 kA here. If your panel was laid out for the 3VA1110, this breaker will not drop in without widening the mounting footprint and verifying the higher SCCR is acceptable.","metaTitle":"Siemens 3VA2010-5KP32-0HA0 SENTRON MCCB, 100 A, 187 kA at 24","metaDescription":"Siemens SENTRON 3VA2010-5KP32-0HA0 molded case circuit breaker, 100 A rated, 187 kA interrupting at 240 V. ETU850 release, shunt trip, communication capable. Current production. So","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"79 kA","at 690 V":"3.4 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"96.25 A","at 60 °C":"92.5 A","at 65 °C":"88.75 A","at 70 °C":"85 A","Trip indicator":"No","Number of poles":"3","Product version":"Line protection","Voltage trigger":"Yes","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"20 000","Undervoltage Release":"No","Communication Function":"Yes","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"13.5 W","Auxiliary contact version":"Without","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"Yes","Rated continuous current Iu":"100 A","Rated insulation voltage Ui":"800 V","Of The Supplied Basic Switch":"3VA2010-5KP32-0AA0","Design of the auxiliary release":"Shunt trip (STL)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9688-0BL30","Design of the overcurrent release":"ETU850","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"25","Adjustable response value time / tr min.":"0.5","Adjustable response value time / tsd max.":"0.5 s","Adjustable response value time / tsd min.":"0.05 s","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"100 A","Adjustable response value current / li max.":"1 200 A","Adjustable response value current / li min.":"150 A","Adjustable response value current / lr min.":"40 A","Adjustable response value current / Isd max.":"1 000 A","Adjustable response value current / Isd min.":"60 A","Neutral conductors / upgradeable/retrofittable":"Yes","Number of CO contacts / for auxiliary contacts":"0","Protective function of the overcurrent release":"LSI","Switching capacity class of the circuit breaker":"M","Max. rated operational current of the frame size":"100 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"Lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"25 x 8.5","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"13 x 1 mm"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=418514&mlfb=3VA2010-5KP32-0HA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2010-5KP32-0HA0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2010-5KP32-0HA0?","answer":"This breaker is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2010-5KP32-0HA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2010-5KP32-0HA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}