{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2010-5KP32-0JL0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2010-5KP32-0JL0","canonicalUrl":"https://aoctrl.com/siemens/3VA2010-5KP32-0JL0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2010-5KP32-0JL0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA series, molded case circuit breaker (MCCB), 3VA2010-5KP32-0JL0, 3-pole, 100 A rated continuous current (Iu), 187 kA interrupting capacity at 240 V, ETU850 electronic trip unit, line protection version, with communication function and shunt trip.","salesMarkdown":"## What the interrupting ratings mean for panel coordination Its interrupting capacity is the headline figure for panel builders: 187 kA at 240 V, 121 kA at 415 V and at 440 V, 79 kA at 500 V, and 3.4 kA at 690 V. ## Thermal derating and continuous current At 55 °C it drops to 96.25 A, at 60 °C to 92.5 A, at 65 °C to 88.75 A, and at 70 °C to 85 A. If your enclosure runs hot (stacked drives, transformer proximity), size the load or the breaker accordingly; the 70 °C figure is the operating maximum, not a storage limit. ## Trip unit, auxiliaries, and communication The overcurrent release is an ETU850 electronic trip unit — programmable, with LSI protection curves (long-time, short-time, instantaneous). It includes a voltage trigger and a trip indicator. A shunt trip (STL) is integrated as the auxiliary release design. The breaker also carries a communication function and an 'other measurement function' — meaning it can report status and measurements over a bus, though the specific protocol isn't listed in this order code's detail. The basic switch sub-assembly is order code 3VA2010-5KP32-0AA0; the integrated auxiliary trip is 3VA9688-0BL32. No undervoltage release, no phase failure detection, and no ground fault monitoring on this variant. The width of 105 mm is standard for a 3-pole 100 A frame in the SENTRON 3VA platform; it will occupy the same DIN or screw-mount footprint as other 3VA 3-pole breakers in this frame size. Maximum power loss is 13.5 W.","metaTitle":"Siemens SENTRON 3VA2010-5KP32-0JL0 MCCB, 100 A, 3-Pole, 187","metaDescription":"Siemens SENTRON 3VA2010-5KP32-0JL0 molded case circuit breaker, 100 A rated, 3-pole, 187 kA at 240 V. ETU850 release, communication capable, shunt trip. Active production, sourced","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"79 kA","at 690 V":"3.4 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"96.25 A","at 60 °C":"92.5 A","at 65 °C":"88.75 A","at 70 °C":"85 A","Trip indicator":"Yes","Number of poles":"3","Product version":"Line protection","Voltage trigger":"Yes","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"20 000","Undervoltage Release":"No","Communication Function":"Yes","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"13.5 W","Auxiliary contact version":"2 auxiliary switches + 1 trip alarm switch + 1 electrical alarm switch HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"Yes","Rated continuous current Iu":"100 A","Rated insulation voltage Ui":"800 V","Of The Supplied Basic Switch":"3VA2010-5KP32-0AA0","Design of the auxiliary release":"Shunt trip (STL)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9688-0BL32","Design of the overcurrent release":"ETU850","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"25","Adjustable response value time / tr min.":"0.5","Adjustable response value time / tsd max.":"0.5 s","Adjustable response value time / tsd min.":"0.05 s","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"100 A","Adjustable response value current / li max.":"1 200 A","Adjustable response value current / li min.":"150 A","Adjustable response value current / lr min.":"40 A","Adjustable response value current / Isd max.":"1 000 A","Adjustable response value current / Isd min.":"60 A","Neutral conductors / upgradeable/retrofittable":"Yes","Number of CO contacts / for auxiliary contacts":"4","Protective function of the overcurrent release":"LSI","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB22","Switching capacity class of the circuit breaker":"M","Max. rated operational current of the frame size":"100 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"Lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"25 x 8.5","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"13 x 1 mm"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=288401&mlfb=3VA2010-5KP32-0JL0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2010-5KP32-0JL0/alternatives.json"},"ai":{"faq":[{"question":"What trip unit does 3VA2010-5KP32-0JL0 use?","answer":"The ETU850 electronic trip unit, which provides programmable LSI protection (long-time, short-time, instantaneous). It includes a voltage trigger and a trip indicator, plus communication and measurement functions."},{"question":"Will 3VA2010-5KP32-0JL0 drop into a panel specified for 3VA1010-2ED32-0JA0?","answer":"The 3VA2010 is a different frame size and rating than the 3VA1010. The 3VA2010 is a 100 A frame with 187 kA interrupting capacity; the 3VA1010 is a smaller frame. Panel cutouts and bus connections differ between the two frame sizes — they are not drop-in interchangeable without rewiring or adapter kits."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2010-5KP32-0JL0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2010-5KP32-0JL0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}