{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2010-5KP32-0KA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2010-5KP32-0KA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2010-5KP32-0KA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2010-5KP32-0KA0","rawCanonicalId":null},"summary":{"shortDescription":"SENTRON 3VA2010-5KP32-0KA0, molded case circuit breaker, 3-pole, line protection, 100 A continuous, 187 kA at 240 V, shunt trip STL, communication function.","salesMarkdown":"That 100 A holds steady even at 70 °C, which is unusual; most breakers start tapering above 40 °C. The interrupting ratings climb to 187 kA at 240 V, drop to 121 kA at 415/440 V, and fall off to 75.6 kA at 500 V, then 3 kA at 690 V. The supplied basic switch is 3VA20105KP320AA0. No trip indicator on the front — you'll know it tripped from the communication signal or the shunt trip circuit. ## Panel fit and environment Max power loss is 13.5 W, so no forced cooling needed in a typical ventilated enclosure. The communication function and shunt trip add wiring, but the depth leaves room behind the door for those connections.","metaTitle":"3VA2010-5KP32-0KA0 SENTRON MCCB, 100 A, 3-Pole, 187 kA at 24","metaDescription":"SENTRON 3VA2010-5KP32-0KA0 molded case circuit breaker, 100 A continuous, 3-pole, 187 kA SCCR at 240 V. Active production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"1 200 A","Minimum":"150 A","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"75.6 kA","at 690 V":"3 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"100 A","at 60 °C":"100 A","at 65 °C":"100 A","at 70 °C":"100 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"Yes","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"13.5 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"Yes","Of The Supplied Basic Switch":"3VA20105KP320AA0","Design Of The Auxiliary Release":"shunt trip (STL)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"100 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU850","protection class IP / on the front":"IP40","design of the N-conductor protection":"adjustable OFF; 20% to 160%","Of The Integrated Auxiliary Trip Unit":"3VA9688-0BL33","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"100 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"M","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=226646&mlfb=3VA2010-5KP32-0KA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2010-5KP32-0KA0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2010-5KP32-0KA0 and how do I get a price?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time."},{"question":"What is 3VA2010-5KP32-0KA0's listed depth?","answer":"The listed depth is 86 mm (3.39 in)."},{"question":"What is 3VA2010-5KP32-0KA0's listed width?","answer":"The listed width is 105 mm (4.13 in)."},{"question":"Will 3VA2010-5KP32-0KA0 drop into a panel that was specified around 3VA2116-5JP32-0AE0 without rewiring?","answer":"Not without checking the mounting and wiring first. The 3VA2116-5JP32-0AE0 is a different frame size and rating — verify the panel cutout, bus bar spacing, and terminal layout against this 3VA2010's 105 mm width and 86 mm depth before assuming a drop-in swap."},{"question":"What compliance documentation does this brand provide for 3VA2010-5KP32-0KA0?","answer":"The evidence does not list specific compliance documents (RoHS, REACH, UL, IEC) for this order code. Typically SENTRON breakers carry UL 489 and IEC 60947-2 certifications, but confirm the exact documentation with the supplier at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2010-5KP32-0KA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2010-5KP32-0KA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}