{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2010-5KP32-0KH0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2010-5KP32-0KH0","canonicalUrl":"https://aoctrl.com/siemens/3VA2010-5KP32-0KH0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2010-5KP32-0KH0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2010-5KP32-0KH0, molded case circuit breaker, 3-pole, 100 A continuous, line protection design, 187 kA at 240 V interrupting rating.","salesMarkdown":"The Siemens SENTRON 3VA2010-5KP32-0KH0 is a 3-pole molded case circuit breaker rated for 100 A continuous current across the full ambient range from 40 °C to 70 °C — no derating needed up to that ceiling. Interrupting capacity climbs to 187 kA at 240 V and holds 121 kA at 415 V and 440 V, then drops to 75.6 kA at 500 V and 3 kA at 690 V. At 690 V the 3 kA limit means it is not a primary choice for 690 V distribution unless the available fault current is known to be low. The shunt trip lets a remote PLC or E-stop relay drop the breaker without a manual handle pull — useful for emergency-off circuits. The trip alarm switch signals a fault trip separately from the auxiliary position feedback, so a control system knows whether the breaker opened on command or on a fault. The 181 mm height leaves space above for a rotary handle mechanism if needed. ## What the 100 A Rating Buys You That is unusual for a thermal-magnetic MCCB; most lose capacity above 40 °C. This one holds 100 A all the way to 70 °C, which simplifies panel design in hot environments (switchgear rooms, outdoor enclosures in sun).","metaTitle":"Siemens 3VA2010-5KP32-0KH0 SENTRON MCCB, 100 A, 3-Pole, Line","metaDescription":"Siemens SENTRON 3VA2010-5KP32-0KH0 molded case circuit breaker, 100 A continuous, 3-pole, 187 kA at 240 V interrupting rating. Current production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"1 200 A","Minimum":"150 A","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"75.6 kA","at 690 V":"3 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"100 A","at 60 °C":"100 A","at 65 °C":"100 A","at 70 °C":"100 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"Yes","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"13.5 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"Yes","Of The Supplied Basic Switch":"3VA20105KP320AA0","Design Of The Auxiliary Switch":"2 auxiliary switches + 1 trip alarm switch HQ","Design Of The Auxiliary Release":"shunt trip (STL)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"100 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU850","protection class IP / on the front":"IP40","design of the N-conductor protection":"adjustable OFF; 20% to 160%","Of The Integrated Auxiliary Trip Unit":"3VA9688-0BL33","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"100 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"3","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB12","Switching Capacity Class Of The Circuit Breaker":"M","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=244381&mlfb=3VA2010-5KP32-0KH0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2010-5KP32-0KH0/alternatives.json"},"ai":{"faq":[{"question":"What is 3VA2010-5KP32-0KH0's listed depth (86 mm) on this component line?","answer":"Depth is 86 mm (3.39 in), width 105 mm (4.13 in), height 181 mm (7.13 in)."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2010-5KP32-0KH0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2010-5KP32-0KH0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}