{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2010-5KP36-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2010-5KP36-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2010-5KP36-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2010-5KP36-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2010-5KP36-0AA0, molded case circuit breaker, 3-pole, 100 A, ETU850 electronic trip unit, line protection design, IP40 front protection.","salesMarkdown":"The interrupting ratings are substantial: 187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 3 kA at 690 V — meaning this breaker can handle high-fault locations without cascading upstream. That is a practical advantage for panels mounted near process heat or in non-conditioned electrical rooms. The 3-pole body fits standard MCCB mounting patterns in SENTRON and third-party distribution panels. Front IP40 protection keeps tools and accidental contact out of the mechanism. ## Deployment context The 100 A rating and high interrupting capacity make it a fit for main or feeder protection in industrial plants, commercial buildings, and infrastructure where fault currents exceed 100 kA at lower voltages. The communication function supports integration with energy management systems for load monitoring and remote tripping.","metaTitle":"Siemens 3VA2010-5KP36-0AA0 SENTRON MCCB, 100 A, 3-Pole, ETU8","metaDescription":"Siemens SENTRON 3VA2010-5KP36-0AA0 molded case circuit breaker, 100 A continuous, 3-pole, ETU850 electronic trip. Interrupting 187 kA at 240 V. Active production, sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"1 200 A","Minimum":"150 A","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"75.6 kA","at 690 V":"3 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"100 A","at 60 °C":"100 A","at 65 °C":"100 A","at 70 °C":"100 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"13.5 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"Yes","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"100 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU850","protection class IP / on the front":"IP40","design of the N-conductor protection":"adjustable OFF; 20% to 160%","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"100 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"M","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"double-sided box terminal","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/45ed7eb7f272ce572caf9b605687cfc5.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=217604&mlfb=3VA2010-5KP36-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2010-5KP36-0AA0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2010-5KP36-0AA0 and how is it quoted?","answer":"This breaker is sourced and quoted to order through independent distribution. Availability and current pricing are confirmed at quote time against an RFQ — no stock or price figures are published here."},{"question":"Will 3VA2010-5KP36-0AA0 drop into a panel designed for 3VA2116-5JP32-0AE0?","answer":"Both are 3-pole SENTRON 3VA MCCBs sharing the same mounting footprint and bus-bar spacing, so a panel designed for the 3VA2116-5JP32-0AE0 will accept this unit without rewiring. The difference is in the trip rating and interrupting capacity — verify the 100 A continuous rating matches your load."},{"question":"What is the interrupting capacity of this MCCB?","answer":"The 3VA2010-5KP36-0AA0 interrupts 187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 3 kA at 690 V. That covers high-fault locations without needing an upstream current-limiting fuse."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2010-5KP36-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2010-5KP36-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}