{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2010-5KP36-0LK0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2010-5KP36-0LK0","canonicalUrl":"https://aoctrl.com/siemens/3VA2010-5KP36-0LK0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2010-5KP36-0LK0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2010-5KP36-0LK0, 3-pole molded case circuit breaker, 160 A maximum, ETU850 electronic trip unit, 187 kA interrupting capacity at 240 V.","salesMarkdown":"The Siemens 3VA2010-5KP36-0LK0 is a 3-pole SENTRON molded case circuit breaker (MCCB) rated for 160 A maximum and 20 A minimum continuous current, fitted with an ETU850 electronic trip unit. The interrupting capacity reaches 187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 3 kA at 690 V — so it clears high-fault currents across common low-voltage distribution voltages without cascading upstream. An undervoltage release and communication function are built in, and the front carries IP40 protection. This is a current-production part (active lifecycle). The 160 A frame covers feeder and large branch circuits; the 20 A minimum setting lets the ETU850 be dialed down to protect smaller loads without swapping the breaker. The 3-pole footprint — 105 mm wide, 181 mm tall, 86 mm deep — fits standard Siemens SENTRON mounting patterns; the 16 W maximum power loss at full load means minimal heat contribution inside a sealed panel.","metaTitle":"Siemens 3VA2010-5KP36-0LK0 SENTRON MCCB, 160 A, 3-Pole, ETU8","metaDescription":"Siemens 3VA2010-5KP36-0LK0 SENTRON MCCB, 160 A max, 3-pole, ETU850 release, 187 kA at 240 V. Active production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"160 A","Minimum":"20 A","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"75.6 kA","at 690 V":"3 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"100 A","at 60 °C":"100 A","at 65 °C":"100 A","at 70 °C":"100 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"Yes","lifecycle_stage":"current","Product Brand Name":"SENTRON","Undervoltage Release":"Yes","Communication Function":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"16 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"Yes","Of The Supplied Basic Switch":"3VA20105KP360AA0","Design Of The Auxiliary Switch":"1 auxiliary switches + 1 trip alarm switch + 1 electrical alarm switch HQ","Design Of The Auxiliary Release":"universal trigger (UNI)","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU850","protection class IP / on the front":"IP40","design of the N-conductor protection":"adjustable OFF; 20% to 160%","Of The Integrated Auxiliary Trip Unit":"3VA9908-0BD12","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"3","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB22","Switching Capacity Class Of The Circuit Breaker":"M","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"double-sided box terminal","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1498437&mlfb=3VA2010-5KP36-0LK0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2010-5KP36-0LK0/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for 3VA2010-5KP36-0LK0?","answer":"We source this part to order against an RFQ. Submit a request and we will confirm availability and current pricing at quote time."},{"question":"What is the interrupting capacity of 3VA2010-5KP36-0LK0 at different voltages?","answer":"At 240 V it is 187 kA; at 415 V and 440 V it is 121 kA; at 500 V it is 75.6 kA; at 690 V it is 3 kA."},{"question":"Does 3VA2010-5KP36-0LK0 include an undervoltage release and communication?","answer":"Yes, both an undervoltage release and a communication function are built into this unit."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2010-5KP36-0LK0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2010-5KP36-0LK0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}