{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2010-5KP46-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2010-5KP46-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2010-5KP46-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2010-5KP46-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2010-5KP46-0AA0, 4-pole molded case circuit breaker, 100 A rated continuous current, ETU850 electronic trip unit, 187 kA at 240 V, 121 kA at 415 V.","salesMarkdown":"It sits in the SENTRON family, which is Siemens' standard line for distribution and motor-circuit protection in industrial panels. Breaking capacity is 187 kA at 240 V AC, 121 kA at 415 V, and 76 kA at 500 V — numbers that put it in the high-interrupting category for a 100 A frame. At 690 V it still clears 3 kA, which covers most 690 V distribution applications. The ETU850 release allows adjustable long-time delay (0.5 to 25 s) and N-conductor protection settings (OFF, 20 % to 100 %), giving selectivity coordination flexibility on a main or feeder breaker. Dimensions: 181 mm height, 140 mm width, 86 mm depth. Maximum power dissipation is 13.5 W at rated load, so ventilation in a sealed enclosure is worth checking if multiple breakers are ganged.","metaTitle":"Siemens 3VA2010-5KP46-0AA0 SENTRON MCCB, 100 A, 4-Pole, 187","metaDescription":"Siemens SENTRON 3VA2010-5KP46-0AA0 molded case circuit breaker, 100 A rated continuous current, 4-pole, ETU850 electronic trip, 187 kA at 240 V. Current lifecycle. Available to ord","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"140 mm","Height":"181 mm","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"76 kA","at 690 V":"3 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"100 A","at 60 °C":"100 A","at 65 °C":"100 A","at 70 °C":"100 A","Depth [in]":"3.4 in","Width [in]":"5.5 in","Height [in]":"7.1 in","Number of poles":"4","Product version":"Line protection","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"20 000","Communication Function":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"13.5 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-40 °C","Other Measurement Function":"Yes","Rated continuous current Iu":"100 A","Rated insulation voltage Ui":"800 V","Ground fault monitoring version":"Without","Design of the overcurrent release":"ETU850","Protection class IP / on the front":"IP40","Design of the N-conductor protection":"adjustable OFF; 20% bis100%","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"25","Adjustable response value time / tr min.":"0.5","Adjustable response value time / tsd max.":"0.5 s","Adjustable response value time / tsd min.":"0.05 s","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"100 A","Adjustable response value current / li max.":"1 200 A","Adjustable response value current / li min.":"150 A","Adjustable response value current / lr min.":"40 A","Adjustable response value current / Isd max.":"1 000 A","Adjustable response value current / Isd min.":"60 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"0","Protective function of the overcurrent release":"LSI","Switching capacity class of the circuit breaker":"M","Max. rated operational current of the frame size":"100 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"box terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, round conductor terminal, stranded":"1 x (6-120 mm²)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/1451a87a397500f1b7abcf46c7efe989.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=234925&mlfb=3VA2010-5KP46-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2010-5KP46-0AA0/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for 3VA2010-5KP46-0AA0?","answer":"Submit an RFQ — we source this part through independent distribution and confirm pricing and lead time at quote time."},{"question":"What is the closest functional second-source to 3VA2010-5KP46-0AA0?","answer":"The peer MPNs 5SQ2670-2YA63 and 5SQ2670-2YA16 are in the same SENTRON family, but the 3VA2010-5KP46-0AA0 uses the ETU850 electronic trip unit — verify the trip curve and accessory compatibility before substituting."},{"question":"What is the depth of the 3VA2010-5KP46-0AA0?","answer":"The body depth is 86 mm (3.4 in)."},{"question":"What compliance documentation does this breaker carry?","answer":"The SENTRON 3VA2 series is typically UL 489, CSA C22.2 No. 5, and IEC 60947-2 listed; specific certification markings for this order code should be confirmed on the nameplate or via the manufacturer's declaration."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2010-5KP46-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2010-5KP46-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}