{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2010-6HL32-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2010-6HL32-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2010-6HL32-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2010-6HL32-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2010-6HL32-0AA0, molded case circuit breaker, 3-pole, 100 A rated continuous current, ETU320 electronic trip unit, 242 kA breaking capacity at 240 V AC.","salesMarkdown":"The Siemens SENTRON 3VA2010-6HL32-0AA0 is a 3-pole molded case circuit breaker (MCCB) rated for 100 A continuous current, with an ETU320 electronic trip unit designed for line protection. At 415 V and 440 V it still holds 187 kA, dropping to 121 kA at 500 V and 3 kA at 690 V, so the SCCR headroom is substantial for most industrial distribution. ## Panel fit and footprint Dimensions are 105 mm wide, 181 mm tall, and 86 mm deep — a standard 3-pole MCCB footprint that fits most DIN-rail or panel-mount enclosures without re-drilling. The 86 mm depth (3.39 in) is shallow enough for shallow backpanels or gland-plate clearance. ## Thermal derating and ambient range The breaker is rated 100 A continuously across the full ambient range from 40 °C to 70 °C — no derating needed up to that ceiling. Operating ambient spans -25 °C to 70 °C, storage from -40 °C to 80 °C. That covers most indoor panel environments, including non-conditioned electrical rooms.","metaTitle":"Siemens 3VA2010-6HL32-0AA0 SENTRON MCCB, 100 A, 242 kA at 24","metaDescription":"Siemens SENTRON 3VA2010-6HL32-0AA0 molded case circuit breaker, 100 A continuous, 242 kA breaking capacity at 240 V. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"1 200 A","Minimum":"150 A","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"3 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"100 A","at 60 °C":"100 A","at 65 °C":"100 A","at 70 °C":"100 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"13.5 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"100 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU320","protection class IP / on the front":"IP40","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"100 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"H","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/83a6d563eedf82ebb925305be6cefd05.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=139693&mlfb=3VA2010-6HL32-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2010-6HL32-0AA0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2010-6HL32-0AA0 and how do I get a price?","answer":"This part is sourced and quoted to order through independent distribution. Submit an RFQ to confirm current pricing and availability — no stock count is held on this page."},{"question":"What is the breaking capacity of 3VA2010-6HL32-0AA0 at 240 V?","answer":"242 kA at 240 V AC, which is the highest interrupting rating on this breaker — suitable for high-fault-current service entrance or large distribution panels."},{"question":"What trip unit does the 3VA2010-6HL32-0AA0 use?","answer":"It uses an ETU320 electronic overcurrent release, designed for line protection (not motor or generator protection)."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2010-6HL32-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2010-6HL32-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}