{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2010-6HL32-0BC0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2010-6HL32-0BC0","canonicalUrl":"https://aoctrl.com/siemens/3VA2010-6HL32-0BC0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2010-6HL32-0BC0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2010-6HL32-0BC0, molded case circuit breaker, 3-pole, 100 A continuous, line protection, with undervoltage release and 2 auxiliary switches HQ.","salesMarkdown":"The Siemens SENTRON 3VA2010-6HL32-0BC0 is a 3-pole molded case circuit breaker rated for 100 A continuous current across the full ambient range from 40 °C to 70 °C — no derating needed up to that ceiling. Interrupting capacity hits 242 kA at 240 V, dropping to 187 kA at 415 V and 440 V, 121 kA at 500 V, and 3 kA at 690 V. That SCCR headroom makes it a strong choice for high-fault distribution panels where selectivity with upstream breakers is critical. The UVR ensures the breaker trips on loss of control voltage, a common requirement in safety circuits and emergency-stop chains. That footprint matches the standard SENTRON 3VA fixed-mount MCCB form factor — direct swap into existing 3VA panel cutouts without re-drilling. Power loss is 16 W maximum — manageable for thermal budgeting in a dense panel. The interrupting ratings (242 kA at 240 V, 187 kA at 415/440 V, 121 kA at 500 V, 3 kA at 690 V) tell you this breaker can clear high fault currents without cascading upstream. For a 480 V distribution board with a transformer secondary fault current of 65 kA, this breaker has nearly 3× headroom — that's selectivity margin.","metaTitle":"Siemens 3VA2010-6HL32-0BC0 MCCB, 100 A, 3-Pole, 242 kA at 24","metaDescription":"Siemens SENTRON 3VA2010-6HL32-0BC0 molded case circuit breaker, 100 A continuous, 3-pole, interrupting up to 242 kA at 240 V. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"1 200 A","Minimum":"150 A","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"3 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"100 A","at 60 °C":"100 A","at 65 °C":"100 A","at 70 °C":"100 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"Yes","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"16 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA20106HL320AA0","Design Of The Auxiliary Switch":"2 auxiliary switches HQ","Design Of The Auxiliary Release":"undervoltage release (UVR)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"100 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU320","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9608-0BB11","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"100 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"2","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA12","Switching Capacity Class Of The Circuit Breaker":"H","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=350716&mlfb=3VA2010-6HL32-0BC0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2010-6HL32-0BC0/alternatives.json"},"ai":{"faq":[{"question":"Will 3VA2010-6HL32-0BC0 drop into a panel specified around 5SQ2370-2YA05 without rewiring?","answer":"The 3VA series uses a different mounting footprint and terminal layout than the 5SQ series. Physical fit is not guaranteed — verify the cutout dimensions and bus bar spacing before ordering. The 3VA is a current-production design; the 5SQ is an older platform."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2010-6HL32-0BC0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2010-6HL32-0BC0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}