{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2010-6HL32-0CH0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2010-6HL32-0CH0","canonicalUrl":"https://aoctrl.com/siemens/3VA2010-6HL32-0CH0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2010-6HL32-0CH0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2010-6HL32-0CH0, molded case circuit breaker, 3-pole, 100 A rated continuous current, 242 kA breaking capacity at 240 V, with undervoltage release and auxiliary switches.","salesMarkdown":"## Siemens SENTRON 3VA2010-6HL32-0CH0 — 100 A MCCB with Undervoltage Release At 240 V the 3VA2010-6HL32-0CH0 clears 242 kA symmetrical — that's a full-range fault rating, not a conditional short-circuit current rating (SCCR). Only at 690 V does it drop to 3 kA, which is typical for a 100 A frame at that voltage. For selectivity coordination downstream of a larger SENTRON feeder, the 100 A continuous rating and the high interrupt capacity let you zone the panel: a 100 A branch can be selectively coordinated with a 400 A main breaker using the manufacturer's selectivity tables, provided the let-through energy of the upstream device is below the withstand rating of this breaker. The 105 mm width means it occupies three standard 35 mm module positions side by side — plan for 108 mm minimum clear width per breaker to allow for wiring gutters on each side. The trip indicator and auxiliary switch terminals are accessible from the front, so you don't need side clearance for status wiring.","metaTitle":"Siemens 3VA2010-6HL32-0CH0 SENTRON MCCB, 100 A, 3-Pole","metaDescription":"Siemens SENTRON 3VA2010-6HL32-0CH0 molded case circuit breaker, 100 A continuous, 3-pole, 242 kA at 240 V. Active production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"1 200 A","Minimum":"150 A","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"3 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"100 A","at 60 °C":"100 A","at 65 °C":"100 A","at 70 °C":"100 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"Yes","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"16 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA20106HL320AA0","Design Of The Auxiliary Switch":"2 auxiliary switches + 1 trip alarm switch HQ","Design Of The Auxiliary Release":"undervoltage release (UVR)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"100 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU320","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9608-0BB24","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"100 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"3","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB12","Switching Capacity Class Of The Circuit Breaker":"H","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=332995&mlfb=3VA2010-6HL32-0CH0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2010-6HL32-0CH0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2010-6HL32-0CH0 and what is the lead time?","answer":"The part is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time — no stock count or lead-time figure is published here."},{"question":"What is the breaking capacity of 3VA2010-6HL32-0CH0 at 240 V?","answer":"It is rated 242 kA symmetrical at 240 V, dropping to 187 kA at 415 V and 440 V, 121 kA at 500 V, and 3 kA at 690 V."},{"question":"Does 3VA2010-6HL32-0CH0 include an undervoltage release?","answer":"Yes, it is equipped with an undervoltage release (UVR) as the auxiliary release, plus two auxiliary switches and one trip alarm switch (HQ)."},{"question":"What are the physical dimensions of 3VA2010-6HL32-0CH0?","answer":"The breaker measures 86 mm deep, 105 mm wide, and 181 mm tall."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2010-6HL32-0CH0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2010-6HL32-0CH0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}