{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2010-6HL32-0DC0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2010-6HL32-0DC0","canonicalUrl":"https://aoctrl.com/siemens/3VA2010-6HL32-0DC0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2010-6HL32-0DC0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON, molded case circuit breaker, 3VA2010-6HL32-0DC0, 3-pole, 100 A continuous, 242 kA at 240 V, 187 kA at 415 V, undervoltage release, 2 HQ auxiliary switches.","salesMarkdown":"The Siemens 3VA2010-6HL32-0DC0 is a SENTRON 3-pole molded case circuit breaker rated for 100 A continuous at 40 °C through 70 °C — no derating needed across that band, which simplifies panel thermal budgeting. ## Interrupting capacity — the real headroom At 240 V this breaker clears 242 kA — that's utility-transformer-level fault current, typical for a main service disconnect. The drop to 3 kA at 690 V tells you this is a 600 V-class frame; don't spec it for 690 V line protection unless the available fault current is known to be under 3 kA. The 100 A continuous rating is flat across 40–70 °C, which is unusual — most MCCBs start derating above 40 °C. That means you can load it to 100 A in a warm enclosure without recalculating. ## Panel fit — dimensions and wiring The 3VA2010-6HL32-0DC0 measures 105 mm wide, 181 mm tall, and 86 mm deep — a standard 3-pole MCCB footprint that fits most DIN-rail or panel-mount enclosures without re-drilling. Two HQ auxiliary switches and the undervoltage release are factory-integrated, so no field wiring of separate modules.","metaTitle":"Siemens 3VA2010-6HL32-0DC0 SENTRON MCCB, 100 A, 242 kA at 24","metaDescription":"Siemens SENTRON 3VA2010-6HL32-0DC0 molded case circuit breaker, 3-pole, 100 A continuous, 242 kA interrupting at 240 V. Current lifecycle. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"1 200 A","Minimum":"150 A","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"3 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"100 A","at 60 °C":"100 A","at 65 °C":"100 A","at 70 °C":"100 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"Yes","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"16 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA20106HL320AA0","Design Of The Auxiliary Switch":"2 auxiliary switches HQ","Design Of The Auxiliary Release":"undervoltage release (UVR)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"100 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU320","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9608-0BB25","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"100 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"2","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA12","Switching Capacity Class Of The Circuit Breaker":"H","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=298817&mlfb=3VA2010-6HL32-0DC0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2010-6HL32-0DC0/alternatives.json"},"ai":{"faq":[{"question":"What is the interrupting capacity of 3VA2010-6HL32-0DC0 at 240 V?","answer":"242 kA at 240 V, dropping to 187 kA at 415 V and 121 kA at 500 V. At 690 V it's 3 kA — verify available fault current before specifying at that voltage."},{"question":"Will 3VA2010-6HL32-0DC0 drop into a panel specified for 3VA1110-5EF32-0AM0?","answer":"Both are 3-pole SENTRON MCCBs with similar frame sizes, but the 3VA2010-6HL32-0DC0 carries 100 A continuous versus the 3VA1110's lower rating. Verify bus bar spacing and lug centers — the 105 mm width is standard, but the integrated UVR and auxiliary switches may change the wiring footprint versus a bare breaker."},{"question":"Where can I buy 3VA2010-6HL32-0DC0?","answer":"Sourced to order against an RFQ through independent distribution. Availability and current pricing confirmed at quote time — no stock figures or lead-time numbers published here."},{"question":"What compliance documentation is available for this MCCB?","answer":"As a Siemens SENTRON product, it carries UL, CSA, and IEC certifications standard for the 3VA series. RoHS and REACH declarations are available from Siemens' documentation portal. Specific cert numbers are not listed in this record."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2010-6HL32-0DC0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2010-6HL32-0DC0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}