{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2010-6HL32-0HC0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2010-6HL32-0HC0","canonicalUrl":"https://aoctrl.com/siemens/3VA2010-6HL32-0HC0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2010-6HL32-0HC0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2010-6HL32-0HC0, molded case circuit breaker, 3-pole, 100 A continuous, line protection, 242 kA at 240 V, 187 kA at 415 V, shunt trip (STL), 2 auxiliary switches HQ.","salesMarkdown":"The interrupting ratings are the headline: 242 kA at 240 V, 187 kA at 415 V and 440 V, 121 kA at 500 V, and 3 kA at 690 V. The basic switch assembly is order code 3VA20106HL320AA0. ## Sizing and selectivity notes The adjustable thermal-magnetic trip unit covers a range from 150 A minimum to 1 200 A maximum. That 150 A minimum is the lowest continuous-current setting; the 1 200 A maximum is the highest short-circuit pickup. For a 100 A continuous load, the trip unit is set at the low end of its range, which gives good coordination with downstream 100 A branch breakers. Maximum power loss is 13.5 W — relevant for panel thermal calculations if multiple breakers are ganged in a small enclosure.","metaTitle":"Siemens SENTRON 3VA2010-6HL32-0HC0 MCCB, 100 A, 3-Pole, 242","metaDescription":"Siemens SENTRON 3VA2010-6HL32-0HC0 molded case circuit breaker, 100 A continuous, 3-pole, 242 kA interrupting at 240 V. Line protection with shunt trip. Current lifecycle, availabl","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"1 200 A","Minimum":"150 A","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"3 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"100 A","at 60 °C":"100 A","at 65 °C":"100 A","at 70 °C":"100 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"Yes","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"13.5 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA20106HL320AA0","Design Of The Auxiliary Switch":"2 auxiliary switches HQ","Design Of The Auxiliary Release":"shunt trip (STL)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"100 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU320","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9688-0BL30","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"100 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"2","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA12","Switching Capacity Class Of The Circuit Breaker":"H","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=3401&mlfb=3VA2010-6HL32-0HC0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2010-6HL32-0HC0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2010-6HL32-0HC0?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What are the key interrupting ratings for 3VA2010-6HL32-0HC0?","answer":"242 kA at 240 V, 187 kA at 415 V and 440 V, 121 kA at 500 V, and 3 kA at 690 V."},{"question":"What is the continuous current rating of 3VA2010-6HL32-0HC0?","answer":"100 A continuous, with no derating needed from 40 °C to 70 °C."},{"question":"Does 3VA2010-6HL32-0HC0 include a shunt trip?","answer":"Yes, it ships with a shunt trip (STL) for remote tripping, plus two HQ auxiliary switches."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2010-6HL32-0HC0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2010-6HL32-0HC0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}