{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2010-6HL32-0JH0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2010-6HL32-0JH0","canonicalUrl":"https://aoctrl.com/siemens/3VA2010-6HL32-0JH0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2010-6HL32-0JH0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2010-6HL32-0JH0, molded case circuit breaker, 3-pole, 100 A, 242 kA at 240 V, line protection, ETU320, shunt trip.","salesMarkdown":"## Line protection MCCB with ETU320 — 100 A, 242 kA breaking capacity Its interrupting capacity reaches 242 kA at 240 V and 187 kA at 415 V and 440 V, stepping down to 121 kA at 500 V and 4 kA at 690 V — figures that define the available fault-current ceiling for selectivity studies on a 400 V distribution board. Thermal derating is documented across the operating range: the breaker holds its full 100 A rating up to 50 °C, then linearly reduces to 96.25 A at 55 °C, 92.5 A at 60 °C, 88.75 A at 65 °C, and 85 A at 70 °C. Maximum power loss is 13.5 W. The breaker mounts in a standard panel footprint with dimensions 86 mm depth, 105 mm width, and 181 mm height — verify cutout and bus-bar spacing before retrofitting into an existing distribution board. ## Compliance documentation As a SENTRON series MCCB, the 3VA2010-6HL32-0JH0 is designed and tested to IEC 60947-2 and carries CE marking for the European market. UL and CSA certifications are standard for the platform; confirm the specific listing for this variant with the manufacturer's declaration of conformity. RoHS and REACH compliance documentation is available from Siemens on request.","metaTitle":"Siemens 3VA2010-6HL32-0JH0 SENTRON MCCB, 100 A, 242 kA at 24","metaDescription":"Siemens SENTRON 3VA2010-6HL32-0JH0 molded case circuit breaker, 100 A rated, 242 kA breaking at 240 V. Line protection, ETU320 release, shunt trip. Current production. Available to","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"4 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"96.25 A","at 60 °C":"92.5 A","at 65 °C":"88.75 A","at 70 °C":"85 A","Trip indicator":"Yes","Number of poles":"3","Product version":"Line protection","Voltage trigger":"Yes","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"20 000","Undervoltage Release":"No","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"13.5 W","Auxiliary contact version":"2 auxiliary switches + 1 trip alarm switch HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"100 A","Rated insulation voltage Ui":"800 V","Of The Supplied Basic Switch":"3VA2010-6HL32-0AA0","Design of the auxiliary release":"Shunt trip (STL)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9688-0BL32","Design of the overcurrent release":"ETU320","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"17","Adjustable response value time / tr min.":"0.5","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"100 A","Adjustable response value current / li max.":"1 200 A","Adjustable response value current / li min.":"150 A","Adjustable response value current / lr min.":"40 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"3","Protective function of the overcurrent release":"LI","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB12","Switching capacity class of the circuit breaker":"H","Max. rated operational current of the frame size":"100 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"Lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"25 x 8.5","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"13 x 1 mm"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=319151&mlfb=3VA2010-6HL32-0JH0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2010-6HL32-0JH0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2010-6HL32-0JH0 and get a price?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Submit a request for quote (RFQ) to confirm availability and current pricing at the time of your order."},{"question":"What is the closest functional second-source for 3VA2010-6HL32-0JH0?","answer":"The peer MPNs 3VA1110-5EE32-0JA0, 3VA1110-5EE32-0DC0, and 3VA1010-4ED32-0AC0 are from the same SENTRON platform but differ in rated current, breaking capacity, and trip-unit configuration. A direct drop-in replacement without rewiring requires verifying the panel cutout dimensions and bus-bar spacing against the 86 mm depth, 105 mm width, and 181 mm height of this unit."},{"question":"What are the key specifications of 3VA2010-6HL32-0JH0?","answer":"Key specs: 3-pole, rated continuous current Iu 100 A, rated insulation voltage Ui 800 V, breaking capacity 242 kA at 240 V / 187 kA at 415 V / 121 kA at 500 V / 4 kA at 690 V, ETU320 electronic trip unit, shunt trip release, 2 auxiliary switches + 1 trip alarm switch, mechanical endurance 20 000 operations, dimensions 86 mm depth × 105 mm width × 181 mm height."},{"question":"What compliance documentation does Siemens provide for this MCCB?","answer":"Siemens provides a declaration of conformity for CE marking under IEC 60947-2, and UL/CSA certifications are standard for the SENTRON platform. RoHS and REACH compliance documentation is available on request from the manufacturer."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2010-6HL32-0JH0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2010-6HL32-0JH0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}