{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2010-6HL32-0KH0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2010-6HL32-0KH0","canonicalUrl":"https://aoctrl.com/siemens/3VA2010-6HL32-0KH0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2010-6HL32-0KH0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2 molded case circuit breaker, 3-pole, 100 A rated continuous current, ETU320 electronic trip unit, line protection, 242 kA breaking capacity at 240 V AC, with shunt trip (STL) and 2 auxiliary switches + 1 trip alarm switch HQ.","salesMarkdown":"The 3VA2010-6HL32-0KH0: The 100 A rating holds flat from 40 °C through 50 °C, then derates to 85 A at 70 °C — so in a warm panel (say 55 °C ambient) you still get 96.25 A continuous. That thermal curve is what a panel builder uses to size the breaker without overspending on copper. The 242 kA at 240 V and 187 kA at 415 V are the interrupting ratings; for a 480 V system the relevant figure is the 500 V line (121 kA), and at 690 V it drops to 4 kA — a reminder that this breaker is built for low-voltage distribution, not 690 V motor circuits. The shunt trip (STL) release is built in — design code 6HL32 signals that. It is a straightforward line-protection MCCB with remote trip capability. Footprint is 105 mm wide × 181 mm high × 86 mm deep — a standard 3-pole MCCB envelope that drops into most SENTRON 3VA2 mounting plates and busbar systems.","metaTitle":"Siemens 3VA2010-6HL32-0KH0 SENTRON MCCB, 100A, 242kA at 240V","metaDescription":"Siemens 3VA2010-6HL32-0KH0 SENTRON molded case circuit breaker, 100A rated continuous current, 242kA breaking at 240V. 3-pole line protection with ETU320 release, shunt trip, and a","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"4 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"96.25 A","at 60 °C":"92.5 A","at 65 °C":"88.75 A","at 70 °C":"85 A","Trip indicator":"Yes","Number of poles":"3","Product version":"Line protection","Voltage trigger":"Yes","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"20 000","Undervoltage Release":"No","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"13.5 W","Auxiliary contact version":"2 auxiliary switches + 1 trip alarm switch HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"100 A","Rated insulation voltage Ui":"800 V","Of The Supplied Basic Switch":"3VA2010-6HL32-0AA0","Design of the auxiliary release":"Shunt trip (STL)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9688-0BL33","Design of the overcurrent release":"ETU320","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"17","Adjustable response value time / tr min.":"0.5","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"100 A","Adjustable response value current / li max.":"1 200 A","Adjustable response value current / li min.":"150 A","Adjustable response value current / lr min.":"40 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"3","Protective function of the overcurrent release":"LI","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB12","Switching capacity class of the circuit breaker":"H","Max. rated operational current of the frame size":"100 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"Lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"25 x 8.5","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"13 x 1 mm"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=153149&mlfb=3VA2010-6HL32-0KH0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2010-6HL32-0KH0/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of 3VA2010-6HL32-0KH0 at 415 V?","answer":"187 kA at 415 V AC. The full breaking-capacity curve is 242 kA at 240 V, 187 kA at 440 V, 121 kA at 500 V, and 4 kA at 690 V."},{"question":"What trip unit does this MCCB use?","answer":"ETU320 electronic overcurrent release. It is a line-protection trip unit — no ground-fault or communication functions on this variant."},{"question":"Does 3VA2010-6HL32-0KH0 include a shunt trip?","answer":"Yes, it includes a shunt trip (STL) release. The auxiliary contact configuration is 2 auxiliary switches plus 1 trip alarm switch (HQ)."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2010-6HL32-0KH0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2010-6HL32-0KH0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}