{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2010-6HL46-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2010-6HL46-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2010-6HL46-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2010-6HL46-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2, molded case circuit breaker, 4-pole, 100 A continuous, ETU320 electronic trip unit, line protection, 242 kA interrupting at 240 V, IP40 front.","salesMarkdown":"## Siemens 3VA2010-6HL46-0AA0 — 100 A SENTRON MCCB with ETU320 That 100 A holds at every 5 °C step, so it's a straight 100 A breaker for most panel environments. The trip range is adjustable between 150 A and 1 200 A — that's the short-circuit and overload pickup window, not the continuous rating. The 100 A continuous frame stays fixed; the ETU320 lets you dial the magnetic/instantaneous threshold within that band to coordinate with downstream devices. Interrupting capacity is the headline here: 242 kA at 240 V, 187 kA at 415 V and 440 V, 121 kA at 500 V, and 3 kA at 690 V. ## Peer comparison — 3VA1110-5ED36-0AA0 The closest functional sibling in the SENTRON family is the 3VA1110-5ED36-0AA0. Both are 4-pole MCCBs with electronic trip units, but the 3VA1110 frame is physically smaller and rated for lower interrupting capacities. The 3VA2010-6HL46-0AA0 carries the higher SCCR (242 kA vs the 3VA1110's typical 65-100 kA range at 240 V) and the wider trip adjustment band. If your panel was specified around a 3VA1110, the 3VA2010 will not drop in without checking the mounting footprint — the 3VA2010 is taller and deeper. Rewiring is not the issue; the bus-bar and enclosure cutout dimensions differ.","metaTitle":"Siemens 3VA2010-6HL46-0AA0 SENTRON MCCB, 100 A, 4-Pole, ETU3","metaDescription":"Siemens 3VA2010-6HL46-0AA0 SENTRON molded case circuit breaker. 100 A continuous, 4-pole, ETU320 trip unit. SCCR 242 kA at 240 V. Current lifecycle. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"140 mm","Height":"181 mm","Maximum":"1 200 A","Minimum":"150 A","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"3 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"100 A","at 60 °C":"100 A","at 65 °C":"100 A","at 70 °C":"100 A","Depth [In]":"3.39 in","Width [In]":"5.51 in","Height [In]":"7.13 in","Trip Indicator":"No","Number Of Poles":"4","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"13.5 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"100 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU320","protection class IP / on the front":"IP40","design of the N-conductor protection":"adjustable OFF; 50%; 100%","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"100 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"H","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"double-sided box terminal","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/010cc839cea29cd4219c7f72cf2e8950.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=443471&mlfb=3VA2010-6HL46-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2010-6HL46-0AA0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2010-6HL46-0AA0 and what is the lead time?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — no stock count or lead-time number is published here, but we can provide a firm quote on request."},{"question":"What is the closest functional second-source to 3VA2010-6HL46-0AA0?","answer":"The closest functional sibling is the 3VA1110-5ED36-0AA0, also a 4-pole SENTRON MCCB with an electronic trip unit. However, the 3VA2010 offers significantly higher interrupting capacity (242 kA vs ~65-100 kA at 240 V) and a wider trip adjustment range. The mounting footprints differ — the 3VA2010 is taller and deeper — so a direct drop-in without enclosure modification is unlikely."},{"question":"What compliance documentation does Siemens provide for 3VA2010-6HL46-0AA0?","answer":"As a SENTRON MCCB, this part carries the standard Siemens compliance documentation including RoHS and REACH declarations, UL listing, and IEC 60947-2 certification. Specific certificates are available on request."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2010-6HL46-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2010-6HL46-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}