{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2010-6HM32-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2010-6HM32-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2010-6HM32-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2010-6HM32-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2010-6HM32-0AA0, molded case circuit breaker, 3-pole, 100 A continuous rating, 242 kA interrupting at 240 V, line protection with ground-fault summation current sensing.","salesMarkdown":"## Siemens SENTRON 3VA2010-6HM32-0AA0 — 100 A MCCB with Ground-Fault Summation Its interrupting capacity reaches 242 kA at 240 V AC, stepping down to 187 kA at 415/440 V and 121 kA at 500 V — at 690 V it still holds 3 kA, covering most industrial voltage levels without needing a current-limiting upstream device. That simplifies panel sizing in warm enclosures or near heat sources. ## Sourcing & Lifecycle — Current Production, No Obsolescence Concern Availability is confirmed through independent distribution channels. Pricing and lead time are quoted per RFQ — the breaker is sourced to order with no supply constraints typical of active Siemens molded-case lines. Same part, different passport: a genuine Siemens unit regardless of which regional Siemens warehouse it ships from. ## Physical Fit — Dimensions and Panel Integration Measures 181 mm height, 105 mm width, and 86 mm depth. Mounts on DIN rail or backplate via integrated screw terminals. No undervoltage release or communication module is factory-installed on this variant (both are optional add-ons). The trip indicator is also absent — this is a basic thermal-magnetic line-protection breaker with ground-fault summation, not a metering or communicating unit. ## Interrupting Capacity and Selectivity Coordination At 415 V the 187 kA rating still covers most industrial transformer secondary faults without requiring a current-limiting fuse upstream. Minimum trip setting is 150 A, maximum 1 200 A. Initial value is 20 A.","metaTitle":"Siemens 3VA2010-6HM32-0AA0 SENTRON MCCB, 100 A, 3-Pole, 242","metaDescription":"Siemens SENTRON 3VA2010-6HM32-0AA0 molded case circuit breaker, 100 A continuous, 3-pole, 242 kA interrupting at 240 V. Line protection with ground-fault summation. Current product","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"1 200 A","Minimum":"150 A","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"3 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"100 A","at 60 °C":"100 A","at 65 °C":"100 A","at 70 °C":"100 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Initial Value":"20 A","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Full-Scale Value":"100 A","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"13.5 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Ground-Fault Monitoring Version":"Summation current formation L-conductor","Continuous Current / Rated Value":"100 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU330","protection class IP / on the front":"IP40","Product Function / Grounding Protection":"Yes","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"100 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LIG","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"H","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/749cb25199db6c154664feedf750440b.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=69938&mlfb=3VA2010-6HM32-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2010-6HM32-0AA0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2010-6HM32-0AA0 and what is the lead time?","answer":"This breaker is sourced to order through independent distribution. Availability and current pricing are confirmed at quote time against an RFQ — no stock count or lead-time number is published here, but the part is actively produced and not constrained."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2010-6HM32-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2010-6HM32-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}