{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2010-6HN32-0AF0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2010-6HN32-0AF0","canonicalUrl":"https://aoctrl.com/siemens/3VA2010-6HN32-0AF0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2010-6HN32-0AF0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA series, molded case circuit breaker, 3VA2010-6HN32-0AF0, 100 A rated continuous current, 3-pole, line protection design, breaking capacity 242 kA at 240 VAC.","salesMarkdown":"The Siemens SENTRON 3VA2010-6HN32-0AF0 is a 3-pole molded case circuit breaker (MCCB) rated for 100 A continuous current across the full ambient temperature range from 40 °C to 70 °C — no derating needed up to the 70 °C mark. Breaking capacity is the headline here: 242 kA at 240 VAC, 187 kA at 415/440 V, 121 kA at 500 V, and 3 kA at 690 V. Depth of 86 mm means it clears most standard enclosure depths (200 mm or deeper) without issue. The auxiliary switch configuration is 1 auxiliary + 1 trip alarm switch HQ, which provides both a status mirror and a separate fault indication contact — useful for remote monitoring or PLC input. ## Electrical characteristics and thermal behavior Maximum power loss is 13.5 W at rated current. The trip indicator is present, so after a fault event you get a visual flag without needing to reset the breaker to check.","metaTitle":"Siemens 3VA2010-6HN32-0AF0 SENTRON MCCB, 100 A, 3-Pole, 242","metaDescription":"Siemens SENTRON 3VA2010-6HN32-0AF0 molded case circuit breaker, 100 A continuous, 3-pole, 242 kA breaking capacity at 240 VAC. Active production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"1 200 A","Minimum":"1 200 A","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"3 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"100 A","at 60 °C":"100 A","at 65 °C":"100 A","at 70 °C":"100 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"13.5 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA20106HN320AA0","Design Of The Auxiliary Switch":"1 auxiliary switch + 1 trip alarm switch HQ","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"100 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU350","protection class IP / on the front":"IP40","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"100 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"2","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB12","Switching Capacity Class Of The Circuit Breaker":"H","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=326408&mlfb=3VA2010-6HN32-0AF0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2010-6HN32-0AF0/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for 3VA2010-6HN32-0AF0?","answer":"Submit an RFQ through this listing. Pricing and stock are confirmed at quote time through independent distribution channels. Availability and current pricing vary with market conditions and are provided on request."},{"question":"What is 3VA2010-6HN32-0AF0's breaking capacity at 240 V?","answer":"242 kA at 240 VAC. At 415/440 V it is 187 kA, at 500 V it is 121 kA, and at 690 V it is 3 kA."},{"question":"Does 3VA2010-6HN32-0AF0 require derating at elevated ambient temperatures?","answer":"No derating is required up to 70 °C. The breaker is rated 100 A continuously from 40 °C through 70 °C ambient."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2010-6HN32-0AF0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2010-6HN32-0AF0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}