{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2010-6HN32-0AH0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2010-6HN32-0AH0","canonicalUrl":"https://aoctrl.com/siemens/3VA2010-6HN32-0AH0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2010-6HN32-0AH0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON series, molded case circuit breaker, 3VA2010-6HN32-0AH0, 3-pole, 100 A rated continuous current, 1200 A frame, 242 kA breaking capacity at 240 V.","salesMarkdown":"## What this MCCB does and the ratings that matter The frame rating is 1200 A, which tells you the physical breaker shell and bus system are sized for that maximum, but the trip unit inside is set for 100 A. Breaking capacity is the headline number here: 242 kA at 240 V, 187 kA at 415 V and 440 V, 121 kA at 500 V, and 3 kA at 690 V. Rated insulation voltage is 800 V, so the internal clearances and creepage distances are designed for 600 V class systems and some 690 V applications, though the breaking capacity at 690 V drops to 3 kA — that's a limitation to watch if you're on a 690 V network. The 86 mm depth includes the arc chute cover and terminals; make sure your enclosure has at least 100 mm clearance in front for the breaker to swing open during maintenance. Panel builders should note that this breaker ships with a trip indicator so you can see at a glance whether it tripped on fault versus being manually switched off. ## Auxiliary switching and accessories That means you get two form-C contacts for status feedback (open/closed) and one dedicated contact that changes state only when the breaker trips on overcurrent or short circuit — useful for remote alarm annunciation. The supplied basic switch is 3VA20106HN320AA0, which is the internal switching mechanism.","metaTitle":"Siemens 3VA2010-6HN32-0AH0 SENTRON MCCB, 100 A, 1200 A frame","metaDescription":"Siemens SENTRON 3VA2010-6HN32-0AH0 molded case circuit breaker, 3-pole, 100 A continuous, 1200 A frame, 242 kA breaking at 240 V. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"1 200 A","Minimum":"1 200 A","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"3 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"100 A","at 60 °C":"100 A","at 65 °C":"100 A","at 70 °C":"100 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"13.5 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA20106HN320AA0","Design Of The Auxiliary Switch":"2 auxiliary switches + 1 trip alarm switch HQ","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"100 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU350","protection class IP / on the front":"IP40","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"100 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"3","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB12","Switching Capacity Class Of The Circuit Breaker":"H","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=68883&mlfb=3VA2010-6HN32-0AH0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2010-6HN32-0AH0/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2010-6HN32-0AH0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2010-6HN32-0AH0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}