{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2010-6HN32-0BA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2010-6HN32-0BA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2010-6HN32-0BA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2010-6HN32-0BA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2010-6HN32-0BA0, molded case circuit breaker, 3-pole, 100 A, 242 kA at 240 V, ETU350 release, undervoltage release.","salesMarkdown":"The Siemens SENTRON 3VA2010-6HN32-0BA0 is a 3-pole molded case circuit breaker (MCCB) rated for 100 A continuous current at 40 °C, with a rated insulation voltage of 800 V. Its headline breaking capacity hits 242 kA at 240 V and 187 kA at 415 V — figures that put it in the high-interrupting class for industrial feeder and distribution panels where fault current runs high. The overcurrent release is an ETU350 electronic trip unit, which gives adjustable long-time, short-time, and instantaneous protection curves. At 415 V the 187 kA interrupting rating is high enough to coordinate with most upstream transformers and downstream distribution breakers without cascading. At 690 V the rating drops to 4 kA — still adequate for 690 V motor circuits, but selectivity planning should account for the reduced margin. The 100 A frame is fully rated at ambient up to 50 °C; above that, derate linearly to 85 A at 70 °C. Dimensions: 105 mm wide, 181 mm high, 86 mm deep. The ETU350 trip unit is field-adjustable via rotary dials on the front face — no software or handheld programmer needed for basic settings.","metaTitle":"Siemens SENTRON 3VA2010-6HN32-0BA0 MCCB, 100 A, 242 kA at 24","metaDescription":"Siemens SENTRON 3VA2010-6HN32-0BA0 molded case circuit breaker, 3-pole, 100 A rated continuous current, 242 kA breaking capacity at 240 V. ETU350 release, undervoltage release. Cur","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"4 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"96.25 A","at 60 °C":"92.5 A","at 65 °C":"88.75 A","at 70 °C":"85 A","Trip indicator":"No","Number of poles":"3","Product version":"Line protection","Voltage trigger":"No","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"20 000","Undervoltage Release":"Yes","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"16 W","Auxiliary contact version":"Without","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"100 A","Rated insulation voltage Ui":"800 V","Of The Supplied Basic Switch":"3VA2010-6HN32-0AA0","Design of the auxiliary release":"Undervoltage release (UVR)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9608-0BB11","Design of the overcurrent release":"ETU350","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"17","Adjustable response value time / tr min.":"0.5","Adjustable response value time / tsd max.":"0.4 s","Adjustable response value time / tsd min.":"0.02 s","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"100 A","Adjustable response value current / li max.":"1 200 A","Adjustable response value current / li min.":"1 200 A","Adjustable response value current / lr min.":"40 A","Adjustable response value current / Isd max.":"1 000 A","Adjustable response value current / Isd min.":"150 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"0","Protective function of the overcurrent release":"LSI","Switching capacity class of the circuit breaker":"H","Max. rated operational current of the frame size":"100 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"Lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"25 x 8.5","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"13 x 1 mm"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=243393&mlfb=3VA2010-6HN32-0BA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2010-6HN32-0BA0/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for 3VA2010-6HN32-0BA0?","answer":"Submit an RFQ through this listing; availability and current pricing are confirmed at quote time through independent distribution channels."},{"question":"What is the breaking capacity of 3VA2010-6HN32-0BA0 at 415 V?","answer":"187 kA at 415 V, which is sufficient for high-fault-current industrial distribution panels."},{"question":"Does 3VA2010-6HN32-0BA0 include an undervoltage release?","answer":"Yes, an undervoltage release (UVR) is integrated as standard, allowing remote tripping on loss of control voltage."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2010-6HN32-0BA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2010-6HN32-0BA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}