{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2010-6HN32-0BC0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2010-6HN32-0BC0","canonicalUrl":"https://aoctrl.com/siemens/3VA2010-6HN32-0BC0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2010-6HN32-0BC0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2010-6HN32-0BC0, molded case circuit breaker, 3-pole, 100 A rated continuous current, 242 kA breaking capacity at 240 V, ETU350 electronic trip unit, undervoltage release, line protection version.","salesMarkdown":"The breaking capacity at 240 V is 242 kA, at 415 V it is 187 kA, and at 690 V it drops to 4 kA — so on a 400 V class panel this breaker handles high fault currents typical of transformer-fed distribution. The breaker is rated 100 A from 40 °C through 50 °C; above that it derates linearly to 85 A at 70 °C. In a closed panel with ambient near 55 °C, expect 96.25 A continuous — so a 100 A feeder should be loaded to about 96 A if the panel runs warm. Mounting is screw-fixed to a backplate or DIN rail adapter; the depth leaves clearance for rear-access busbars in a typical 600 mm deep enclosure. ## What the ETU350 release and undervoltage release mean for coordination The breaker does not include a voltage trigger, phase failure detection, or communication function — it is a standalone protective device, not a smart breaker.","metaTitle":"Siemens 3VA2010-6HN32-0BC0 SENTRON MCCB, 100A, 242kA at 240V","metaDescription":"Siemens SENTRON 3VA2010-6HN32-0BC0 molded case circuit breaker, 100A rated continuous current, 242kA breaking capacity at 240V. ETU350 release, undervoltage release included. Curre","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"4 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"96.25 A","at 60 °C":"92.5 A","at 65 °C":"88.75 A","at 70 °C":"85 A","Trip indicator":"No","Number of poles":"3","Product version":"Line protection","Voltage trigger":"No","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"20 000","Undervoltage Release":"Yes","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"16 W","Auxiliary contact version":"2 auxiliary switches HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"100 A","Rated insulation voltage Ui":"800 V","Of The Supplied Basic Switch":"3VA2010-6HN32-0AA0","Design of the auxiliary release":"Undervoltage release (UVR)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9608-0BB11","Design of the overcurrent release":"ETU350","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"17","Adjustable response value time / tr min.":"0.5","Adjustable response value time / tsd max.":"0.4 s","Adjustable response value time / tsd min.":"0.02 s","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"100 A","Adjustable response value current / li max.":"1 200 A","Adjustable response value current / li min.":"1 200 A","Adjustable response value current / lr min.":"40 A","Adjustable response value current / Isd max.":"1 000 A","Adjustable response value current / Isd min.":"150 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"2","Protective function of the overcurrent release":"LSI","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA12","Switching capacity class of the circuit breaker":"H","Max. rated operational current of the frame size":"100 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"Lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"25 x 8.5","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"13 x 1 mm"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=255932&mlfb=3VA2010-6HN32-0BC0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2010-6HN32-0BC0/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of 3VA2010-6HN32-0BC0 at 415 V?","answer":"The breaking capacity at 415 V is 187 kA, matching the 440 V rating."},{"question":"Where can I buy 3VA2010-6HN32-0BC0?","answer":"This part is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commitment."},{"question":"What compliance documentation does Siemens provide for this MCCB?","answer":"The 3VA series carries IEC 60947-2 certification for molded case circuit breakers; the specific approvals (UL, CSA, CE, UKCA, EAC) are listed on the manufacturer's declaration of conformity. RoHS and REACH compliance declarations are standard for current-production SENTRON breakers."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2010-6HN32-0BC0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2010-6HN32-0BC0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}