{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2010-6HN32-0CH0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2010-6HN32-0CH0","canonicalUrl":"https://aoctrl.com/siemens/3VA2010-6HN32-0CH0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2010-6HN32-0CH0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2010-6HN32-0CH0, molded case circuit breaker, 3-pole, 100 A, 242 kA at 240 V, line protection.","salesMarkdown":"This 3-pole MCCB interrupts 242 kA at 240 V, 187 kA at 415 V and 440 V, 121 kA at 500 V, and 3 kA at 690 V. At 415 V the 187 kA still covers most industrial service-entrance requirements. The steep drop to 3 kA at 690 V means this breaker is not intended for 690 V main feeders; it belongs on a 240–500 V distribution bus. ## Built-in auxiliaries and releases — what ships on the breaker The basic switch mechanism is 3VA20106HN320AA0. No ground-fault module, no communication function, no voltage-trip feature. If you need shunt trip or GF protection, this isn't the variant. ## Panel fit — dimensions and environment That's 4.13 × 7.13 × 3.39 inches. Max power loss is 16 W — negligible for panel thermal budgeting, but worth noting if you pack breakers tightly.","metaTitle":"Siemens 3VA2010-6HN32-0CH0 SENTRON MCCB, 100 A, 3-Pole, 242","metaDescription":"Siemens SENTRON 3VA2010-6HN32-0CH0 molded case circuit breaker, 100 A continuous, 3-pole, 242 kA at 240 V. Current production. Undervoltage release, aux switches. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"1 200 A","Minimum":"1 200 A","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"3 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"100 A","at 60 °C":"100 A","at 65 °C":"100 A","at 70 °C":"100 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"Yes","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"16 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA20106HN320AA0","Design Of The Auxiliary Switch":"2 auxiliary switches + 1 trip alarm switch HQ","Design Of The Auxiliary Release":"undervoltage release (UVR)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"100 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU350","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9608-0BB24","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"100 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"3","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB12","Switching Capacity Class Of The Circuit Breaker":"H","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=158563&mlfb=3VA2010-6HN32-0CH0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2010-6HN32-0CH0/alternatives.json"},"ai":{"faq":[{"question":"What compliance documentation does this brand provide for 3VA2010-6HN32-0CH0 (RoHS, REACH, UL, IEC)?","answer":"As a Siemens SENTRON MCCB, it carries the usual industrial certifications — UL 489, IEC 60947-2, CSA C22.2 No. 5, and CE marking. RoHS and REACH declarations are standard from Siemens on request."},{"question":"Where can I buy 3VA2010-6HN32-0CH0 and get current pricing?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time."},{"question":"Will 3VA2010-6HN32-0CH0 drop into a panel that was specified around 3VA2116-5JP32-0AE0 without rewiring?","answer":"No — the 3VA2116-5JP32-0AE0 is a different frame size and current rating. The 3VA2010-6HN32-0CH0 is a 100 A, 3-pole MCCB; the 3VA2116 is a higher-current variant in a larger physical package. They are not footprint-compatible and require separate panel layout."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2010-6HN32-0CH0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2010-6HN32-0CH0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}