{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2010-6HN32-0JL0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2010-6HN32-0JL0","canonicalUrl":"https://aoctrl.com/siemens/3VA2010-6HN32-0JL0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2010-6HN32-0JL0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2010-6HN32-0JL0, molded case circuit breaker, 3-pole, 100 A, interrupting ratings 242 kA at 240 V, 187 kA at 415 V, ETU350 release.","salesMarkdown":"## MCCB with ETU350 — line protection for high-fault panels The Siemens SENTRON 3VA2010-6HN32-0JL0 is a 3-pole molded case circuit breaker (MCCB) rated for line protection with a continuous current Iu of 100 A at 40 °C. Its interrupting capacity reaches 242 kA at 240 V and 187 kA at 415 V — figures that cover most industrial service-entrance and distribution panels where fault currents run high. The breaker measures 105 mm wide, 181 mm high, and 86 mm deep — a footprint that fits standard SENTRON 3VA panel cutouts. The 105 mm width is the same as other 3VA2 frame sizes, so a panel designed for a 3VA1010-2ED32-0JA0 will accept this unit without re-drilling or busbar rework, provided the incoming cable lugs and busbar spacing match the 100 A rating. ## Auxiliary and trip accessories Factory-fitted with a shunt trip release (STL) and an auxiliary contact block comprising 2 auxiliary switches, 1 trip alarm switch, and 1 electrical alarm switch HQ. This configuration supports remote tripping and status feedback without additional wiring modifications. Rated continuous current holds at 100 A from 40 °C up to 50 °C. Above 50 °C, derate linearly: 96.25 A at 55 °C, 92.5 A at 60 °C, 88.75 A at 65 °C, and 85 A at 70 °C. Maximum power loss is 13.5 W. Storage range spans -40 °C to 80 °C; operating ambient is -25 °C to 70 °C. These limits govern panel layout and ventilation requirements — a tightly packed enclosure may need forced airflow to stay below 50 °C at full load.","metaTitle":"Siemens 3VA2010-6HN32-0JL0 SENTRON MCCB, 100 A, 242 kA at 24","metaDescription":"Siemens SENTRON 3VA2010-6HN32-0JL0 molded case circuit breaker, 100 A rated continuous current, 242 kA interrupting at 240 V. Active production, quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"4 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"96.25 A","at 60 °C":"92.5 A","at 65 °C":"88.75 A","at 70 °C":"85 A","Trip indicator":"Yes","Number of poles":"3","Product version":"Line protection","Voltage trigger":"Yes","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"20 000","Undervoltage Release":"No","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"13.5 W","Auxiliary contact version":"2 auxiliary switches + 1 trip alarm switch + 1 electrical alarm switch HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"100 A","Rated insulation voltage Ui":"800 V","Of The Supplied Basic Switch":"3VA2010-6HN32-0AA0","Design of the auxiliary release":"Shunt trip (STL)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9688-0BL32","Design of the overcurrent release":"ETU350","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"17","Adjustable response value time / tr min.":"0.5","Adjustable response value time / tsd max.":"0.4 s","Adjustable response value time / tsd min.":"0.02 s","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"100 A","Adjustable response value current / li max.":"1 200 A","Adjustable response value current / li min.":"1 200 A","Adjustable response value current / lr min.":"40 A","Adjustable response value current / Isd max.":"1 000 A","Adjustable response value current / Isd min.":"150 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"4","Protective function of the overcurrent release":"LSI","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB22","Switching capacity class of the circuit breaker":"H","Max. rated operational current of the frame size":"100 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"Lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"25 x 8.5","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"13 x 1 mm"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=48387&mlfb=3VA2010-6HN32-0JL0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2010-6HN32-0JL0/alternatives.json"},"ai":{"faq":[{"question":"Who supplies 3VA2010-6HN32-0JL0 and how is it quoted for volume purchases?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for your required quantity."},{"question":"Will 3VA2010-6HN32-0JL0 drop into a panel specified around 3VA1010-2ED32-0JA0 without rewiring?","answer":"Yes — both breakers share the same 105 mm width and SENTRON 3VA frame footprint, so the panel cutout and busbar spacing are compatible. Verify that the 100 A rating matches your cable and lug sizing."},{"question":"What are the interrupting ratings of this MCCB?","answer":"242 kA at 240 V, 187 kA at 415 V and 440 V, 121 kA at 500 V, and 4 kA at 690 V."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2010-6HN32-0JL0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2010-6HN32-0JL0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}