{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2010-6HN32-0KH0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2010-6HN32-0KH0","canonicalUrl":"https://aoctrl.com/siemens/3VA2010-6HN32-0KH0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2010-6HN32-0KH0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2010-6HN32-0KH0, molded case circuit breaker, 3-pole, 100 A, line protection, with shunt trip and auxiliary switches.","salesMarkdown":"The Siemens SENTRON 3VA2010-6HN32-0KH0 is a 3-pole molded case circuit breaker (MCCB) rated for 100 A continuous current across the full ambient range from 40 °C to 70 °C — no derating needed up to that ceiling. At 690 V the rating drops to 3 kA, so this is not a 690 V main breaker — keep it on the 240–500 V side for full fault-clearing capability. The shunt trip lets a remote signal — from an E-stop, fire alarm, or PLC safety output — open the breaker electrically without someone at the handle. The auxiliary switches report the breaker's open/closed state back to a control system, and the trip alarm flags that it opened on a fault, not manually. No undervoltage release is fitted, so if you need UVR for a motor starter interlock, this is not the order code. Dimensions are 181 mm high, 105 mm wide, 86 mm deep — a standard 3-pole MCCB footprint that fits most DIN-rail or panel-mount enclosures sized for 100 A frames. No communication module or ground-fault monitoring is built in; this is a straight thermal-magnetic or electronic trip unit for line protection only.","metaTitle":"Siemens 3VA2010-6HN32-0KH0 SENTRON MCCB, 100 A, 3-Pole, 242","metaDescription":"Siemens SENTRON 3VA2010-6HN32-0KH0 molded case circuit breaker, 100 A continuous, 3-pole, 242 kA breaking at 240 V. Active production. Sourced to order. Request RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"1 200 A","Minimum":"1 200 A","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"3 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"100 A","at 60 °C":"100 A","at 65 °C":"100 A","at 70 °C":"100 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"Yes","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"13.5 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA20106HN320AA0","Design Of The Auxiliary Switch":"2 auxiliary switches + 1 trip alarm switch HQ","Design Of The Auxiliary Release":"shunt trip (STL)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"100 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU350","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9688-0BL33","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"100 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"3","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB12","Switching Capacity Class Of The Circuit Breaker":"H","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=302702&mlfb=3VA2010-6HN32-0KH0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2010-6HN32-0KH0/alternatives.json"},"ai":{"faq":[{"question":"How do I get pricing and availability for 3VA2010-6HN32-0KH0?","answer":"Submit an RFQ through this listing. The part is sourced to order through independent distribution; current pricing and stock position are confirmed at quote time."},{"question":"What is the breaking capacity at 240 V and 415 V?","answer":"242 kA at 240 V and 187 kA at 415 V. At 690 V the capacity drops to 3 kA, so this breaker is best applied on 240–500 V systems for full fault-clearing performance."},{"question":"Will 3VA2010-6HN32-0KH0 drop into a panel built for 5SQ2370-2YA05?","answer":"Not without a layout review. The 5SQ2370 series belongs to an older Siemens MCCB family with different mounting dimensions and accessory wiring. The 3VA is the current SENTRON platform; verify panel cutouts and busbar spacing before substitution."},{"question":"What auxiliary switches and releases are fitted?","answer":"This variant includes a shunt trip (STL) for remote opening, two auxiliary switches for status indication, and one trip-alarm switch (HQ) that signals a fault trip. No undervoltage release is present."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2010-6HN32-0KH0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2010-6HN32-0KH0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}