{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2010-6HN32-0KL0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2010-6HN32-0KL0","canonicalUrl":"https://aoctrl.com/siemens/3VA2010-6HN32-0KL0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2010-6HN32-0KL0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA series molded case circuit breaker, 3VA2010-6HN32-0KL0, 100 A continuous, 3-pole, 242 kA breaking capacity at 240 V, line protection design.","salesMarkdown":"The Siemens SENTRON 3VA2010-6HN32-0KL0 is a 3-pole molded case circuit breaker (MCCB) rated for 100 A continuous current across the full ambient range from 40 °C to 70 °C — no derating needed up to that ceiling. Its breaking capacity is 242 kA at 240 V, 187 kA at 415 V and 440 V, and 121 kA at 500 V, dropping to 3 kA at 690 V. Designed for line protection, this MCCB carries a shunt trip release (STL) and a complement of auxiliary switches: two auxiliary switches, one trip alarm switch, and one electrical alarm switch (HQ designation). The trip indicator and voltage trigger are present; undervoltage release and ground-fault monitoring are not fitted on this variant. Panel integration is straightforward — the 105 mm width, 181 mm height, and 86 mm depth fit standard SENTRON 3VA mounting footprints. Maximum power loss is 13.5 W, so thermal budgeting inside the enclosure is manageable.","metaTitle":"Siemens SENTRON 3VA2010-6HN32-0KL0 MCCB, 100 A, 3-Pole, 242","metaDescription":"Siemens SENTRON 3VA2010-6HN32-0KL0 molded case circuit breaker, 100 A continuous, 3-pole, 242 kA breaking at 240 V. Active production. Sourced to order. Request RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"1 200 A","Minimum":"1 200 A","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"3 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"100 A","at 60 °C":"100 A","at 65 °C":"100 A","at 70 °C":"100 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"Yes","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"13.5 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA20106HN320AA0","Design Of The Auxiliary Switch":"2 auxiliary switches + 1 trip alarm switch + 1 electrical alarm switch HQ","Design Of The Auxiliary Release":"shunt trip (STL)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"100 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU350","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9688-0BL33","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"100 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"4","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB22","Switching Capacity Class Of The Circuit Breaker":"H","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=473297&mlfb=3VA2010-6HN32-0KL0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2010-6HN32-0KL0/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of this MCCB at 415 V?","answer":"187 kA at 415 V, which is the same rating as at 440 V. At 240 V it reaches 242 kA."},{"question":"How do I get current pricing and availability for 3VA2010-6HN32-0KL0?","answer":"Submit an RFQ through this listing — availability and current pricing are confirmed at quote time through independent distribution channels."},{"question":"Does this MCCB include a shunt trip release?","answer":"Yes, it is fitted with a shunt trip (STL) release, plus two auxiliary switches, one trip alarm switch, and one electrical alarm switch."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2010-6HN32-0KL0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2010-6HN32-0KL0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}