{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2010-6HN36-0AG0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2010-6HN36-0AG0","canonicalUrl":"https://aoctrl.com/siemens/3VA2010-6HN36-0AG0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2010-6HN36-0AG0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2010-6HN36-0AG0, molded case circuit breaker, 3-pole, 100 A, ETU350 electronic trip unit, line protection version.","salesMarkdown":"## What the 100 A rating means for your panel Above 50 °C the curve steps down: 96.25 A at 55 °C, 92.5 A at 60 °C, 88.75 A at 65 °C, and 85 A at 70 °C. The ETU350 gives you adjustable thermal and magnetic pickup settings via the front dials — not a fixed thermal bimetal, so you can fine-tune coordination downstream without swapping the breaker body. Rated insulation voltage Ui is 800 V, and the interrupting ratings climb steeply at lower voltages: 242 kA at 240 V, 187 kA at 415 V and 440 V, 121 kA at 500 V, and 4 kA at 690 V (–). It will hold coordination with upstream gear under most plant fault scenarios. Standard DIN-rail or screw-mount backplate. The auxiliary contact configuration is 1 auxiliary switch + 1 trip alarm switch (HP type), which gives you one N/O or N/C signal for status and a separate alarm contact that closes only on a trip event. That alarm contact is useful for a remote annunciator or PLC input to flag a faulted breaker without polling the main trip coil. Maximum power loss is 13.5 W.","metaTitle":"Siemens 3VA2010-6HN36-0AG0 SENTRON MCCB, 100 A, 3-Pole, ETU3","metaDescription":"Siemens SENTRON 3VA2010-6HN36-0AG0 molded case circuit breaker, 100 A rated, 3-pole, ETU350 release. 242 kA at 240 V. Current lifecycle. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"4 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"96.25 A","at 60 °C":"92.5 A","at 65 °C":"88.75 A","at 70 °C":"85 A","Trip indicator":"Yes","Number of poles":"3","Product version":"Line protection","Voltage trigger":"No","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"20 000","Undervoltage Release":"No","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"13.5 W","Auxiliary contact version":"1 auxiliary switch + 1 trip alarm switch HP","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"100 A","Rated insulation voltage Ui":"800 V","Of The Supplied Basic Switch":"3VA2010-6HN36-0AA0","Design of the auxiliary release":"Without auxiliary release","Ground fault monitoring version":"Without","Design of the overcurrent release":"ETU350","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"17","Adjustable response value time / tr min.":"0.5","Adjustable response value time / tsd max.":"0.4 s","Adjustable response value time / tsd min.":"0.02 s","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"100 A","Adjustable response value current / li max.":"1 200 A","Adjustable response value current / li min.":"1 200 A","Adjustable response value current / lr min.":"40 A","Adjustable response value current / Isd max.":"1 000 A","Adjustable response value current / Isd min.":"150 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"2","Protective function of the overcurrent release":"LSI","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB11","Switching capacity class of the circuit breaker":"H","Max. rated operational current of the frame size":"100 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"box terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, round conductor terminal, stranded":"1 x (6-120 mm²)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=401111&mlfb=3VA2010-6HN36-0AG0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2010-6HN36-0AG0/alternatives.json"},"ai":{"faq":[{"question":"What are the physical dimensions of 3VA2010-6HN36-0AG0?","answer":"105 mm wide, 181 mm tall, 86 mm deep. Standard DIN-rail or screw-mount backplate compatible with the 3VL footprint."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2010-6HN36-0AG0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2010-6HN36-0AG0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}