{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2010-6HN36-0BC0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2010-6HN36-0BC0","canonicalUrl":"https://aoctrl.com/siemens/3VA2010-6HN36-0BC0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2010-6HN36-0BC0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2010-6HN36-0BC0, molded case circuit breaker (MCCB), 3-pole, 100 A rated continuous current (Iu), ETU350 electronic trip unit, breaking capacity 242 kA at 240 V AC.","salesMarkdown":"The Siemens SENTRON 3VA2010-6HN36-0BC0 is a 3-pole molded case circuit breaker (MCCB) rated for 100 A continuous current (Iu) without derating up to 50 °C — above that, it steps down to 96.25 A at 55 °C, 92.5 A at 60 °C, 88.75 A at 65 °C, and 85 A at 70 °C, so plan your thermal budget if the breaker sits in a hot enclosure. Breaking capacity hits 242 kA at 240 V AC and 187 kA at 415/440 V, then drops to 121 kA at 500 V and 4 kA at 690 V — the 240 V figure is the headline, but the 415 V rating is the one that governs most industrial distribution panels in Europe and Asia. ## Panel fit: dimensions and integration The 86 mm depth leaves room for rear-connected busbars or cable lugs in a shallow enclosure. ## Undervoltage release and auxiliary contacts The 2 HQ auxiliary switches provide independent NO/NC contacts for remote status indication; they're wired separately from the main power path, so the PLC sees the breaker state even if the UVR has already opened it. No voltage trigger or trip indicator on the front face, so you'll rely on the aux contacts or the ETU's local LED for trip indication.","metaTitle":"Siemens 3VA2010-6HN36-0BC0 SENTRON MCCB, 100 A, 3-Pole, ETU3","metaDescription":"Siemens SENTRON 3VA2010-6HN36-0BC0 molded case circuit breaker, 100 A rated continuous current, 3-pole, ETU350 electronic trip, 242 kA at 240 V. Active production. Available to ord","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"4 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"96.25 A","at 60 °C":"92.5 A","at 65 °C":"88.75 A","at 70 °C":"85 A","Trip indicator":"No","Number of poles":"3","Product version":"Line protection","Voltage trigger":"No","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"20 000","Undervoltage Release":"Yes","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"16 W","Auxiliary contact version":"2 auxiliary switches HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"100 A","Rated insulation voltage Ui":"800 V","Of The Supplied Basic Switch":"3VA2010-6HN36-0AA0","Design of the auxiliary release":"Undervoltage release (UVR)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9608-0BB11","Design of the overcurrent release":"ETU350","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"17","Adjustable response value time / tr min.":"0.5","Adjustable response value time / tsd max.":"0.4 s","Adjustable response value time / tsd min.":"0.02 s","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"100 A","Adjustable response value current / li max.":"1 200 A","Adjustable response value current / li min.":"1 200 A","Adjustable response value current / lr min.":"40 A","Adjustable response value current / Isd max.":"1 000 A","Adjustable response value current / Isd min.":"150 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"2","Protective function of the overcurrent release":"LSI","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA12","Switching capacity class of the circuit breaker":"H","Max. rated operational current of the frame size":"100 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"box terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, round conductor terminal, stranded":"1 x (6-120 mm²)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=96662&mlfb=3VA2010-6HN36-0BC0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2010-6HN36-0BC0/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of 3VA2010-6HN36-0BC0 at different voltages?","answer":"It delivers 242 kA at 240 V AC, 187 kA at 415 V and 440 V, 121 kA at 500 V, and 4 kA at 690 V. The 415 V rating is the practical one for most European and Asian 400 V distribution panels."},{"question":"What trip unit does the 3VA2010-6HN36-0BC0 use?","answer":"It uses the ETU350 electronic trip unit, which provides adjustable overload (L) and short-circuit (S, I) protection curves. This lets you coordinate with downstream breakers without swapping fixed-trip elements."},{"question":"Does 3VA2010-6HN36-0BC0 include an undervoltage release?","answer":"Yes, it comes with an integrated undervoltage release (UVR), part number 3VA9608-0BB11, which trips the breaker when control voltage drops. This is critical for safety circuits that must fail open on loss of control power."},{"question":"Where can I buy 3VA2010-6HN36-0BC0?","answer":"This part is sourced to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm offer."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2010-6HN36-0BC0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2010-6HN36-0BC0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}