{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2010-6HN36-0BH0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2010-6HN36-0BH0","canonicalUrl":"https://aoctrl.com/siemens/3VA2010-6HN36-0BH0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2010-6HN36-0BH0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2 molded case circuit breaker, 3VA2010-6HN36-0BH0, 3-pole, 100 A, ETU350 line protection, with undervoltage release and HQ auxiliary switches.","salesMarkdown":"Breaking capacity runs from 242 kA at 240 V down to 4 kA at 690 V — the 242 kA figure at 240 V is the headline interrupt rating, meaning this breaker can safely clear a fault of that magnitude at that voltage without welding contacts or rupturing the case. The 3VA2 frame is the compact, high-performance tier of the SENTRON MCCB family, designed for panel builders who need high interrupting capacity in a standard footprint. Above 50 °C it steps down: 96.25 A at 55 °C, 92.5 A at 60 °C, 88.75 A at 65 °C, and 85 A at 70 °C. The 690 V breaking capacity is 4 kA. The ETU350 trip unit is an electronic (not thermal-magnetic) release, which gives better accuracy and adjustable trip settings. It is configured for line protection — meaning it protects cables and busbars, not motor overloads — and has no voltage trigger or communication function. ## Where it goes in the panel Dimensions are 181 mm high, 105 mm wide, 86 mm deep — the 105 mm width is a standard 3-pole MCCB footprint that fits most panel layouts without re-spacing busbars. Maximum power loss is 16 W at rated current — a modest figure that keeps heat rise manageable in a closed panel, but worth checking against your enclosure's thermal budget if you are ganging several breakers. The basic switch (the breaker without auxiliaries) is order code 3VA2010-6HN36-0AA0, and the integrated auxiliary trip module is 3VA9608-0BB11. If you are stocking spares, those sub-assemblies are the service-level components.","metaTitle":"Siemens 3VA2010-6HN36-0BH0 SENTRON MCCB, 100 A, 3-Pole, ETU3","metaDescription":"Siemens 3VA2010-6HN36-0BH0 SENTRON molded case circuit breaker, 100 A rated current, 3-pole, ETU350 electronic trip unit, 242 kA at 240 V. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"4 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"96.25 A","at 60 °C":"92.5 A","at 65 °C":"88.75 A","at 70 °C":"85 A","Trip indicator":"Yes","Number of poles":"3","Product version":"Line protection","Voltage trigger":"No","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"20 000","Undervoltage Release":"Yes","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"16 W","Auxiliary contact version":"2 auxiliary switches + 1 trip alarm switch HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"100 A","Rated insulation voltage Ui":"800 V","Of The Supplied Basic Switch":"3VA2010-6HN36-0AA0","Design of the auxiliary release":"Undervoltage release (UVR)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9608-0BB11","Design of the overcurrent release":"ETU350","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"17","Adjustable response value time / tr min.":"0.5","Adjustable response value time / tsd max.":"0.4 s","Adjustable response value time / tsd min.":"0.02 s","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"100 A","Adjustable response value current / li max.":"1 200 A","Adjustable response value current / li min.":"1 200 A","Adjustable response value current / lr min.":"40 A","Adjustable response value current / Isd max.":"1 000 A","Adjustable response value current / Isd min.":"150 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"3","Protective function of the overcurrent release":"LSI","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB12","Switching capacity class of the circuit breaker":"H","Max. rated operational current of the frame size":"100 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"box terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, round conductor terminal, stranded":"1 x (6-120 mm²)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=536535&mlfb=3VA2010-6HN36-0BH0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2010-6HN36-0BH0/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2010-6HN36-0BH0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2010-6HN36-0BH0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}