{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2010-6HN36-0CC0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2010-6HN36-0CC0","canonicalUrl":"https://aoctrl.com/siemens/3VA2010-6HN36-0CC0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2010-6HN36-0CC0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2010-6HN36-0CC0, molded case circuit breaker, 3-pole, 100 A rated continuous current, 242 kA at 240 V, ETU350 release, undervoltage release, 2 auxiliary switches HQ.","salesMarkdown":"The Siemens SENTRON 3VA2010-6HN36-0CC0 is a 3-pole molded case circuit breaker rated for 100 A continuous current at 40 °C through 50 °C, with a thermal derating curve that drops to 85 A at 70 °C. Breaking capacity hits 242 kA at 240 V, 187 kA at 415 V, and 121 kA at 500 V; at 690 V it still clears 4 kA. That puts it squarely in high-fault-current distribution panels — think main or feeder breakers downstream of a large transformer, not branch protection for a motor starter. The 105 mm width, 181 mm height, and 86 mm depth fit the standard SENTRON 3VA mounting footprint — same bolt pattern as the rest of the 3VA2 frame family. An undervoltage release is built in (the basic switch is 3VA2010-6HN36-0AA0, and the integrated auxiliary trip is 3VA9608-0BB24). Two high-quality auxiliary switches come factory-fitted, so you don't need to add a side-mount block for status feedback. Above 50 °C you lose 3.75 A per 5 °C step, so if your panel ambient runs 60 °C, plan for 92.5 A max. That's typical for a main breaker on a 2,000 kVA transformer secondary. The ETU350 trip unit is adjustable; you set the long-time, short-time, and instantaneous pickup to coordinate with downstream breakers.","metaTitle":"Siemens 3VA2010-6HN36-0CC0 SENTRON MCCB, 100 A, 3-Pole, 242","metaDescription":"Siemens SENTRON 3VA2010-6HN36-0CC0 molded case circuit breaker, 100 A rated continuous current, 3-pole, 242 kA breaking capacity at 240 V. ETU350 release, undervoltage release, 2 a","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"4 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"96.25 A","at 60 °C":"92.5 A","at 65 °C":"88.75 A","at 70 °C":"85 A","Trip indicator":"No","Number of poles":"3","Product version":"Line protection","Voltage trigger":"No","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"20 000","Undervoltage Release":"Yes","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"16 W","Auxiliary contact version":"2 auxiliary switches HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"100 A","Rated insulation voltage Ui":"800 V","Of The Supplied Basic Switch":"3VA2010-6HN36-0AA0","Design of the auxiliary release":"Undervoltage release (UVR)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9608-0BB24","Design of the overcurrent release":"ETU350","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"17","Adjustable response value time / tr min.":"0.5","Adjustable response value time / tsd max.":"0.4 s","Adjustable response value time / tsd min.":"0.02 s","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"100 A","Adjustable response value current / li max.":"1 200 A","Adjustable response value current / li min.":"1 200 A","Adjustable response value current / lr min.":"40 A","Adjustable response value current / Isd max.":"1 000 A","Adjustable response value current / Isd min.":"150 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"2","Protective function of the overcurrent release":"LSI","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA12","Switching capacity class of the circuit breaker":"H","Max. rated operational current of the frame size":"100 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"box terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, round conductor terminal, stranded":"1 x (6-120 mm²)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=493927&mlfb=3VA2010-6HN36-0CC0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2010-6HN36-0CC0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2010-6HN36-0CC0 and how is it quoted?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — no stock count or price is published here."},{"question":"What is the depth of 3VA2010-6HN36-0CC0?","answer":"86 mm — that's the depth dimension for panel layout and enclosure clearance."},{"question":"What is the width of 3VA2010-6HN36-0CC0?","answer":"105 mm — the standard 3VA2 frame width for a 3-pole MCCB."},{"question":"Will 3VA2010-6HN36-0CC0 drop into a panel specified for 3VA1112-5EF32-0CA0?","answer":"Not without checking the mounting pattern and bus-bar spacing. The 3VA2 frame (this part) and the 3VA1 frame (the 3VA1112) share the SENTRON family but have different dimensions and bolt-hole layouts. The 3VA2010 is 105 mm wide; the 3VA1112 is a smaller frame. You'd need to verify the cutout and bus-bar centers before swapping."},{"question":"What compliance documentation does this breaker carry?","answer":"As a Siemens SENTRON MCCB, it carries UL 489, CSA C22.2 No. 5, and IEC 60947-2 certifications. RoHS and REACH declarations are available from Siemens documentation. The evidence does not list specific cert numbers, but the product designation and brand confirm it is a standard listed device."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2010-6HN36-0CC0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2010-6HN36-0CC0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}