{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2010-6HN36-0DL0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2010-6HN36-0DL0","canonicalUrl":"https://aoctrl.com/siemens/3VA2010-6HN36-0DL0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2010-6HN36-0DL0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2010-6HN36-0DL0, molded case circuit breaker, 3-pole, 100 A continuous, 242 kA interrupting at 240 V, line protection design, undervoltage release, 86 mm depth.","salesMarkdown":"The Siemens SENTRON 3VA2010-6HN36-0DL0 is a 3-pole molded case circuit breaker (MCCB) rated for 100 A continuous current across the full ambient range from 40 °C to 70 °C — no derating needed within that span, per the datasheet. Interrupting capacity is 242 kA at 240 V, 187 kA at 415 V and 440 V, 121 kA at 500 V, and 3 kA at 690 V. The trip indicator is present, and there is no voltage-trigger function or communication module on this variant. The width and height are standard for a 100 A 3-pole MCCB in the SENTRON 3VA platform; it mounts via the standard DIN-rail or screw-mount pattern typical of this frame size. ## Electrical characteristics and thermal limits Maximum power loss is 16 W. As a Siemens SENTRON product, this MCCB carries the standard compliance documentation for industrial control gear: CE marking for the European market, and UL/CSA listing for North American installations. RoHS and REACH declarations are available from the manufacturer. No ground-fault monitoring version is included on this order code.","metaTitle":"Siemens SENTRON 3VA2010-6HN36-0DL0 MCCB, 100A, 3-Pole, 242kA","metaDescription":"Siemens SENTRON 3VA2010-6HN36-0DL0 molded case circuit breaker, 100A continuous, 3-pole, 242kA interrupting at 240V. Line protection with UVR. Current production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"1 200 A","Minimum":"1 200 A","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"3 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"100 A","at 60 °C":"100 A","at 65 °C":"100 A","at 70 °C":"100 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"Yes","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"16 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA20106HN360AA0","Design Of The Auxiliary Switch":"2 auxiliary switches + 1 trip alarm switch + 1 electrical alarm switch HQ","Design Of The Auxiliary Release":"undervoltage release (UVR)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"100 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU350","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9608-0BB25","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"100 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"4","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB22","Switching Capacity Class Of The Circuit Breaker":"H","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"double-sided box terminal","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=207850&mlfb=3VA2010-6HN36-0DL0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2010-6HN36-0DL0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2010-6HN36-0DL0 and how do I get a price?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm quote."},{"question":"When sourcing 3VA2010-6HN36-0DL0, what's the closest functional second-source — 3VA1110-5EF32-0AM0?","answer":"The 3VA1110-5EF32-0AM0 is a different frame size and rating within the same SENTRON 3VA family. It will not drop into the same panel cutout or bus connection without re-engineering the mounting and bus bars. The 3VA2010-6HN36-0DL0 is a 100 A, 3-pole line-protection breaker with UVR and a specific auxiliary switch complement; the 3VA1110 series is a smaller frame. Verify your panel's ampacity and physical footprint before substituting."},{"question":"What is 3VA2010-6HN36-0DL0's listed depth (86 mm) on this component line?","answer":"The depth is 86 mm (3.39 in). This is the body depth; allow additional clearance for wiring and cable bending radius behind the breaker."},{"question":"What is 3VA2010-6HN36-0DL0's listed width (105 mm) on this component line?","answer":"The width is 105 mm (4.13 in). This is the standard width for a 3-pole 100 A MCCB in the SENTRON 3VA platform."},{"question":"Will 3VA2010-6HN36-0DL0 drop into a panel that was specified around 3VA1110-5EF32-0AM0 without rewiring?","answer":"No. The 3VA1110 series is a physically smaller frame with different mounting dimensions and bus-bar spacing. The 3VA2010-6HN36-0DL0 is a larger 100 A frame; it will not fit the same cutout or bus connection without panel rework."},{"question":"What compliance documentation does this brand provide for 3VA2010-6HN36-0DL0 (RoHS, REACH, UL, IEC)?","answer":"Siemens provides CE marking, UL/CSA listing, and RoHS/REACH declarations for the SENTRON 3VA series. Specific documentation can be obtained from the manufacturer or through your sourcing channel."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2010-6HN36-0DL0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2010-6HN36-0DL0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}