{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2010-6HN36-0HL0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2010-6HN36-0HL0","canonicalUrl":"https://aoctrl.com/siemens/3VA2010-6HN36-0HL0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2010-6HN36-0HL0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2010-6HN36-0HL0, molded case circuit breaker, 3-pole, 100 A continuous, 242 kA breaking capacity at 240 V, line protection, shunt trip, 2 aux + 2 alarm switches.","salesMarkdown":"The Siemens SENTRON 3VA2010-6HN36-0HL0 is a 3-pole molded case circuit breaker rated for 100 A continuous current across the full operating temperature range of -25 °C to 70 °C — no derating needed up to that ceiling. Breaking capacity hits 242 kA at 240 V, 187 kA at 415 V, and 121 kA at 500 V, with a steep drop to 3 kA at 690 V. That 242 kA figure at 240 V puts it in the high-interrupting class for industrial main feeders or large sub-distribution where fault currents are serious. The shunt trip (STL) and the auxiliary switch pack — 2 aux + 1 trip alarm + 1 electrical alarm HQ — mean it can be wired into a remote-trip or status-monitoring circuit without an add-on module. Dimensions are 105 mm wide, 181 mm high, 86 mm deep — standard 3-pole MCCB footprint for a 100 A frame. ## How the auxiliary switch pack and shunt trip change the wiring The supplied basic switch is 3VA20106HN360AA0. The auxiliary release is a shunt trip (STL) — that means a separate control voltage (typically 110–240 V AC/DC) energizes the trip coil to remotely open the breaker. The trip alarm switch changes state only when the breaker trips on fault, not on manual open — useful for a separate alarm circuit. The electrical alarm switch HQ is a high-qualified signal for remote indication. Wire the shunt trip to a pushbutton or PLC output; the aux switches can feed status back to a DI card. ## Panel fit and thermal management At 105 mm wide, this breaker fits a standard 3-pole MCCB cutout. Depth is 86 mm — check the back-of-panel clearance for the shunt trip wiring and auxiliary switch terminals. Maximum power loss is 13.5 W at rated current; that's low enough that no forced cooling is needed in a ventilated enclosure, but if you're packing multiple breakers in a small cabinet, sum the losses and check the temperature rise against the 70 °C operating max.","metaTitle":"Siemens SENTRON 3VA2010-6HN36-0HL0 MCCB, 100 A, 3-Pole, 242","metaDescription":"Siemens SENTRON 3VA2010-6HN36-0HL0 molded case circuit breaker, 100 A continuous, 3-pole, breaking capacity 242 kA at 240 V. Active production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"1 200 A","Minimum":"1 200 A","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"3 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"100 A","at 60 °C":"100 A","at 65 °C":"100 A","at 70 °C":"100 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"Yes","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"13.5 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA20106HN360AA0","Design Of The Auxiliary Switch":"2 auxiliary switches + 1 trip alarm switch + 1 electrical alarm switch HQ","Design Of The Auxiliary Release":"shunt trip (STL)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"100 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU350","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9688-0BL30","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"100 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"4","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB22","Switching Capacity Class Of The Circuit Breaker":"H","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"double-sided box terminal","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=84791&mlfb=3VA2010-6HN36-0HL0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2010-6HN36-0HL0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2010-6HN36-0HL0 and get a price?","answer":"We source this part through independent distribution. Submit an RFQ; availability and current pricing are confirmed at quote time."},{"question":"What compliance documentation does Siemens provide for 3VA2010-6HN36-0HL0?","answer":"As a SENTRON molded case circuit breaker, it is designed to meet IEC 60947-2 and UL 489 standards. RoHS and REACH declarations are standard from Siemens. Specific certificates are available on request."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2010-6HN36-0HL0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2010-6HN36-0HL0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}