{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2010-6HN36-0JL0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2010-6HN36-0JL0","canonicalUrl":"https://aoctrl.com/siemens/3VA2010-6HN36-0JL0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2010-6HN36-0JL0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2 molded case circuit breaker, 3VA2010-6HN36-0JL0, 3-pole, 100 A, line protection, ETU350 electronic trip unit, shunt trip (STL), 2 aux + 1 trip alarm + 1 electrical alarm HQ.","salesMarkdown":"The 3VA2010-6HN36-0JL0: This MCCB delivers 242 kA interrupting rating at 240 V, dropping to 187 kA at 415 V and 440 V, then 121 kA at 500 V, and 4 kA at 690 V. The 4 kA at 690 V still covers most industrial 690 V distribution, but selectivity studies at that voltage need the lower ceiling. ## Trip unit and auxiliary contacts The ETU350 electronic trip unit provides LSI protection (long-time, short-time, instantaneous) with adjustable settings. A shunt trip (STL) release is built in for remote tripping. ## Thermal derating and environment Rated 100 A from 40 °C through 50 °C, then derates linearly to 85 A at 70 °C. Maximum power loss is 13.5 W.","metaTitle":"Siemens 3VA2010-6HN36-0JL0 SENTRON MCCB, 100 A, 3-Pole, ETU3","metaDescription":"Siemens 3VA2010-6HN36-0JL0 SENTRON molded case circuit breaker, 100 A rated, 3-pole, ETU350 trip unit, 242 kA at 240 V. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"4 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"96.25 A","at 60 °C":"92.5 A","at 65 °C":"88.75 A","at 70 °C":"85 A","Trip indicator":"Yes","Number of poles":"3","Product version":"Line protection","Voltage trigger":"Yes","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"20 000","Undervoltage Release":"No","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"13.5 W","Auxiliary contact version":"2 auxiliary switches + 1 trip alarm switch + 1 electrical alarm switch HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"100 A","Rated insulation voltage Ui":"800 V","Of The Supplied Basic Switch":"3VA2010-6HN36-0AA0","Design of the auxiliary release":"Shunt trip (STL)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9688-0BL32","Design of the overcurrent release":"ETU350","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"17","Adjustable response value time / tr min.":"0.5","Adjustable response value time / tsd max.":"0.4 s","Adjustable response value time / tsd min.":"0.02 s","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"100 A","Adjustable response value current / li max.":"1 200 A","Adjustable response value current / li min.":"1 200 A","Adjustable response value current / lr min.":"40 A","Adjustable response value current / Isd max.":"1 000 A","Adjustable response value current / Isd min.":"150 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"4","Protective function of the overcurrent release":"LSI","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB22","Switching capacity class of the circuit breaker":"H","Max. rated operational current of the frame size":"100 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"box terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, round conductor terminal, stranded":"1 x (6-120 mm²)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=385225&mlfb=3VA2010-6HN36-0JL0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2010-6HN36-0JL0/alternatives.json"},"ai":{"faq":[{"question":"What is the interrupting rating of 3VA2010-6HN36-0JL0 at 240 V?","answer":"242 kA at 240 V. That is the highest interrupting rating in its voltage range, suitable for high-fault service entrance applications."},{"question":"What trip unit does this MCCB use?","answer":"The ETU350 electronic trip unit with LSI protection (long-time, short-time, instantaneous). It also has a built-in shunt trip (STL) for remote tripping."},{"question":"Where can I buy 3VA2010-6HN36-0JL0 and how is it quoted?","answer":"Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2010-6HN36-0JL0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2010-6HN36-0JL0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}