{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2010-6HN36-0KH0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2010-6HN36-0KH0","canonicalUrl":"https://aoctrl.com/siemens/3VA2010-6HN36-0KH0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2010-6HN36-0KH0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON molded case circuit breaker, 3VA2010-6HN36-0KH0, 3-pole, 100 A continuous, 242 kA interrupting at 240 V, line protection design with shunt trip and auxiliary switches.","salesMarkdown":"That 100 A holds flat through every temperature step in the evidence, so it's a genuine 100 A frame, not a derated 125 A. The interrupting ratings are substantial: 242 kA at 240 V, 187 kA at 415 V and 440 V, 121 kA at 500 V, and 3 kA at 690 V. ## Auxiliaries and trip accessories That means you can remotely trip the breaker from a safety circuit or E-stop chain, and you get status feedback — open/closed and tripped — back to the PLC or annunciator panel. The auxiliary switch design is built into the breaker, not a field-add-on kit, so the wiring is already accounted for in the 86 mm depth × 105 mm width × 181 mm height envelope. No undervoltage release on this order code, and no ground-fault monitoring module. If you need UVR or GF protection, that's a different variant in the 3VA family. The supplied basic switch is 3VA20106HN360AA0, which is the internal switching mechanism — the complete breaker assembly is what ships. Mounts in a standard panel or enclosure on a mounting plate — it is a molded case breaker, not a DIN-rail snap-on unit, so plan for bolt-down installation. Maximum power loss is 13.5 W, which is modest for a 100 A frame — ventilation in the enclosure is still advisable if other heat sources are nearby. For that, look at the 3VA2 with communication options.","metaTitle":"Siemens 3VA2010-6HN36-0KH0 SENTRON MCCB, 100 A, 3-Pole, 242","metaDescription":"Siemens SENTRON 3VA2010-6HN36-0KH0 molded case circuit breaker, 100 A continuous, 3-pole, 242 kA at 240 V. Current production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"1 200 A","Minimum":"1 200 A","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"3 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"100 A","at 60 °C":"100 A","at 65 °C":"100 A","at 70 °C":"100 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"Yes","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"13.5 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA20106HN360AA0","Design Of The Auxiliary Switch":"2 auxiliary switches + 1 trip alarm switch HQ","Design Of The Auxiliary Release":"shunt trip (STL)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"100 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU350","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9688-0BL33","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"100 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"3","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB12","Switching Capacity Class Of The Circuit Breaker":"H","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"double-sided box terminal","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=343635&mlfb=3VA2010-6HN36-0KH0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2010-6HN36-0KH0/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2010-6HN36-0KH0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2010-6HN36-0KH0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}