{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2010-6JP32-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2010-6JP32-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2010-6JP32-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2010-6JP32-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA molded case circuit breaker, order code 3VA2010-6JP32-0AA0, 100 A, 3-pole, ETU550 electronic trip unit, 242 kA breaking capacity at 240 V.","salesMarkdown":"The Siemens 3VA2010-6JP32-0AA0 is a SENTRON 3VA molded case circuit breaker (MCCB) in the line-protection version, rated for a permanent current of 100 A across the full ambient range of -25 °C to 70 °C. Breaking capacity is the headline: 242 kA at 240 V, 187 kA at 415 V and 440 V, 121 kA at 500 V, and 3 kA at 690 V. The ETU550 electronic trip unit allows adjustable N-conductor protection (OFF or 20 % to 160 % of the rated current), and the unit includes a communication function for integration into a plant-wide power monitoring system. The 3VA2010-6JP32-0AA0 is a fixed-pattern MCCB designed for panel mounting. The ETU550 release provides adjustable long-time, short-time, instantaneous, and ground-fault protection curves — set these per the coordination study before commissioning. The communication function (likely PROFIBUS or PROFINET via a communication module) enables remote trip indication and current metering. No trip indicator is fitted on this variant, so fault diagnostics rely on the communication interface or a separate status contact.","metaTitle":"Siemens 3VA2010-6JP32-0AA0 SENTRON MCCB, 100 A, 3-pole, ETU5","metaDescription":"Siemens 3VA2010-6JP32-0AA0 SENTRON 3VA molded case circuit breaker, 100 A, 3-pole, 242 kA at 240 V, ETU550 release, current lifecycle stage, quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"3 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"100 A","at 60 °C":"100 A","at 65 °C":"100 A","at 70 °C":"100 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"No","Number Of Poles":"3","Product version":"Line protection","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Communication Function":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"13.5 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","rated insulation voltage Ui":"800 V","Courant permanent assigné Iu":"100 A","Ground-Fault Monitoring Version":"Without","Design Of The Overcurrent Release":"ETU550","protection class IP / on the front":"IP40","design of the N-conductor protection":"adjustable OFF; 20% to 160%","reference code / acc. to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"Yes","Adjustable response value current / li max.":"1 200 A","Adjustable response value current / li min.":"150 A","Neutral conductors / upgradeable/retrofittable":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"H","Max. rated operational current of the frame size":"100 A","Mechanical Service Life (Switching Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"25 x 8 mm","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"13 x 1 mm"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/589e8c9b0eb188ab21910d95c529e47a.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=274624&mlfb=3VA2010-6JP32-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2010-6JP32-0AA0/alternatives.json"},"ai":{"faq":[{"question":"What trip unit does 3VA2010-6JP32-0AA0 use?","answer":"The ETU550 electronic trip unit, which provides adjustable long-time, short-time, instantaneous, and ground-fault protection, plus adjustable N-conductor protection from OFF to 20 % to 160 % of the rated current."},{"question":"Does 3VA2010-6JP32-0AA0 have a communication function?","answer":"Yes, this variant includes a communication function, enabling remote monitoring and integration into a power management system via a compatible communication module."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2010-6JP32-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2010-6JP32-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}