{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2010-6KP32-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2010-6KP32-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2010-6KP32-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2010-6KP32-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA molded case circuit breaker, 3VA2010-6KP32-0AA0, 3-pole, 100 A, ETU850 electronic trip unit, line protection, 242 kA at 240 V.","salesMarkdown":"## What this MCCB delivers Breaking capacity is substantial: 242 kA at 240 V, 187 kA at 415 V and 440 V, 121 kA at 500 V, and 3 kA at 690 V. The 86 mm depth means it clears most shallow enclosure back-panels; verify your gland plate clearance if the breaker mounts near the rear wall. ## Trip unit and protection capabilities The ETU850 electronic trip unit supports communication and additional measurement functions — it can report load current and event data over the integrated communication interface, which is useful for energy monitoring or predictive maintenance schemes. Ground-fault monitoring is not built in; that requires an external module or a different variant. Front protection is IP40, suitable for indoor panel installation where no washdown or dust ingress is expected. Power dissipation at rated current is 13.5 W maximum — factor that into your enclosure thermal budget, especially in densely packed panels with multiple breakers.","metaTitle":"Siemens 3VA2010-6KP32-0AA0 SENTRON MCCB, 100 A, 3-Pole, ETU8","metaDescription":"Siemens 3VA2010-6KP32-0AA0 SENTRON molded case circuit breaker, 100 A continuous, 3-pole, ETU850 electronic trip unit. Breaking capacity 242 kA at 240 V. Active production, sourced","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"1 200 A","Minimum":"150 A","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"3 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"100 A","at 60 °C":"100 A","at 65 °C":"100 A","at 70 °C":"100 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"13.5 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"Yes","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"100 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU850","protection class IP / on the front":"IP40","design of the N-conductor protection":"adjustable OFF; 20% to 160%","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"100 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"H","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/9d7fc619e16719197896e97eb396afcd.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=219922&mlfb=3VA2010-6KP32-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2010-6KP32-0AA0/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of this MCCB at 415 V?","answer":"187 kA at 415 V, which covers most industrial 400 V panelboard fault-current requirements without needing an upstream current-limiting fuse."},{"question":"Will 3VA2010-6KP32-0AA0 fit in a panel designed for 5SQ2370-2YA05?","answer":"Both are 3-pole MCCBs in the 100 A class, but the 3VA2010-6KP32-0AA0 uses the SENTRON 3VA platform footprint (105 mm wide, 86 mm deep) while the 5SQ2370 series belongs to a different generation. Panel cutouts and bus-bar centers may differ — verify the mounting dimensions against your existing back-panel layout before ordering."},{"question":"How do I get current pricing and availability for 3VA2010-6KP32-0AA0?","answer":"Submit an RFQ through this listing. Pricing and stock are confirmed at quote time through our independent distribution network — no automated figures are published here."},{"question":"What compliance documentation does Siemens provide for this breaker?","answer":"The SENTRON 3VA series carries IEC 60947-2 certification as a molded case circuit breaker. RoHS and REACH declarations are standard with the manufacturer's documentation package. Specific UL listing status should be confirmed on the nameplate variant; this order code is primarily designed for IEC markets."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2010-6KP32-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2010-6KP32-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}