{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2010-6KP36-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2010-6KP36-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2010-6KP36-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2010-6KP36-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2010-6KP36-0AA0 molded case circuit breaker, 3-pole, 100 A, 242 kA at 240 V, ETU850 electronic trip unit, IP40 front, active production.","salesMarkdown":"## Interrupting capacity and selectivity — the real constraint The Siemens SENTRON 3VA2010-6KP36-0AA0 is a 3-pole molded case circuit breaker rated for 100 A continuous current with a flat derating curve from 40 °C through 70 °C — no reduction needed across the typical panel ambient range. The headline interrupting ratings are 242 kA at 240 V AC, 187 kA at 415 V and 440 V, 121 kA at 500 V, and 3 kA at 690 V. The steep drop to 3 kA at 690 V tells you this is a 600 V class frame, not a 690 V design; at that voltage the breaker relies on the ETU850's fast reaction time rather than brute magnetic repulsion. ## ETU850 trip unit — what it does for coordination The electronic trip unit ETU850 provides adjustable overload (Ir) and short-time (Isd) protection. The neutral protection is adjustable OFF or from 20 % to 160 % of the phase setting. The communication function integrates with SENTRON powermanagement software for remote monitoring. The 3-pole design with no undervoltage release and no voltage trigger means it is a straight thermal-magnetic + electronic breaker — no auxiliary shunt trip or UVR coil to wire.","metaTitle":"Siemens 3VA2010-6KP36-0AA0 SENTRON MCCB, 100 A, 242 kA at 24","metaDescription":"Siemens SENTRON 3VA2010-6KP36-0AA0 molded case circuit breaker, 100 A continuous, 242 kA interrupting at 240 V. ETU850 release. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"3 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"100 A","at 60 °C":"100 A","at 65 °C":"100 A","at 70 °C":"100 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"No","Number Of Poles":"3","Product version":"Line protection","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Communication Function":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"13.5 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"Yes","rated insulation voltage Ui":"800 V","Courant permanent assigné Iu":"100 A","Ground-Fault Monitoring Version":"Without","Design Of The Overcurrent Release":"ETU850","protection class IP / on the front":"IP40","design of the N-conductor protection":"adjustable OFF; 20% to 160%","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"Yes","Adjustable response value current / li max.":"1 200 A","Adjustable response value current / li min.":"150 A","Neutral conductors / upgradeable/retrofittable":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"H","Max. rated operational current of the frame size":"100 A","Mechanical Service Life (Switching Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"double-sided box terminal","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal","Type of connectable conductor cross-section, round conductor terminal, stranded":"1 x (6 - 120 mm²)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=194280&mlfb=3VA2010-6KP36-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2010-6KP36-0AA0/alternatives.json"},"ai":{"faq":[{"question":"Does 3VA2010-6KP36-0AA0 include ground-fault monitoring?","answer":"No, this variant ships without ground-fault monitoring hardware. The ETU850 trip unit can support it, but the ground-fault monitoring version is not fitted on this order code."},{"question":"What is the depth of this MCCB?","answer":"86 mm (3.39 in) deep, with width 105 mm (4.13 in) and height 181 mm (7.13 in)."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2010-6KP36-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2010-6KP36-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}