{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2010-6KP46-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2010-6KP46-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2010-6KP46-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2010-6KP46-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2010-6KP46-0AA0, molded case circuit breaker, 4-pole, 100 A, ETU850 electronic trip unit, breaking capacity 242 kA at 240 V.","salesMarkdown":"The interrupting ratings tell you where this breaker can be installed without cascading upstream. At 240 V it clears 242 kA — that's utility-grade fault current, typical for a main or large feeder in a 240 V distribution board. At 415 V and 440 V it still holds 187 kA, and at 500 V it manages 121 kA. The drop to 3 kA at 690 V means it is not a 690 V main breaker — at that voltage it protects a downstream branch with limited fault current.","metaTitle":"Siemens 3VA2010-6KP46-0AA0 SENTRON MCCB, 100 A, 4-Pole, ETU8","metaDescription":"Siemens 3VA2010-6KP46-0AA0 SENTRON molded case circuit breaker, 100 A rated, 4-pole, ETU850 electronic trip unit, breaking capacity up to 242 kA at 240 V. Active production. Source","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"140 mm","Height":"181 mm","Maximum":"1 200 A","Minimum":"150 A","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"3 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"100 A","at 60 °C":"100 A","at 65 °C":"100 A","at 70 °C":"100 A","Depth [In]":"3.39 in","Width [In]":"5.51 in","Height [In]":"7.13 in","Trip Indicator":"No","Number Of Poles":"4","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"13.5 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"Yes","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"100 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU850","protection class IP / on the front":"IP40","design of the N-conductor protection":"adjustable OFF; 20% to 100%","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"100 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"H","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"double-sided box terminal","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/d7e19668148b3d67893878ae6b0ddd2d.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=201151&mlfb=3VA2010-6KP46-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2010-6KP46-0AA0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2010-6KP46-0AA0 and get a price?","answer":"We source this MCCB to order against an RFQ. Submit a request for quote through our site; availability and current pricing are confirmed at quote time."},{"question":"What are the key ratings of 3VA2010-6KP46-0AA0?","answer":"Rated continuous current is 100 A with no derating from 40 °C to 70 °C. Breaking capacity reaches 242 kA at 240 V, 187 kA at 415/440 V, 121 kA at 500 V, and 3 kA at 690 V. It is a 4-pole MCCB with an ETU850 electronic trip unit and communication capability."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2010-6KP46-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2010-6KP46-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}