{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2010-7HN36-0AK0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2010-7HN36-0AK0","canonicalUrl":"https://aoctrl.com/siemens/3VA2010-7HN36-0AK0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2010-7HN36-0AK0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA series, molded case circuit breaker, order code 3VA2010-7HN36-0AK0, 100 A continuous, 3-pole, 330 kA breaking capacity at 240 V.","salesMarkdown":"It carries a continuous rated current of 100 A across the full ambient temperature range from 40 °C to 70 °C — no derating needed up to that ceiling, which simplifies panel sizing in warm enclosures. The 100 A rating is the same at every point from 40 °C through 70 °C, so a panel builder can populate this breaker at the top of a warm cabinet without recalculating thermal limits. Breaking capacity hits 330 kA at 240 V, 242 kA at 415 V and 440 V, 187 kA at 500 V, and 3 kA at 690 V — the 240 V figure is the headline for high-fault residential or light commercial services; the 415 V/440 V numbers cover the common European low-voltage distribution level. Dimensions are 86 mm deep, 105 mm wide, 181 mm high — a standard 3-pole MCCB footprint that drops into most SENTRON or third-party distribution boards without enclosure modification. ## Auxiliary switch complement and monitoring A trip indicator is present on the front face, giving a local visual confirmation that the breaker opened on fault rather than being manually switched off. No last-time-buy notice, no successor part number has been issued.","metaTitle":"Siemens 3VA2010-7HN36-0AK0 SENTRON MCCB, 100 A, 3-Pole, 330","metaDescription":"Siemens SENTRON 3VA2010-7HN36-0AK0 molded case circuit breaker, 100 A continuous, 3-pole, 330 kA at 240 V. Active production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"1 200 A","Minimum":"1 200 A","at 240 V":"330 kA","at 415 V":"242 kA","at 440 V":"242 kA","at 500 V":"187 kA","at 690 V":"3 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"100 A","at 60 °C":"100 A","at 65 °C":"100 A","at 70 °C":"100 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"7.7 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA20107HN360AA0","Design Of The Auxiliary Switch":"1 auxiliary switches + 1 trip alarm switch + 1 electrical alarm switch HQ","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"100 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU350","protection class IP / on the front":"IP40","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"100 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"3","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB22","Switching Capacity Class Of The Circuit Breaker":"C","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"double-sided box terminal","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1421027&mlfb=3VA2010-7HN36-0AK0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2010-7HN36-0AK0/alternatives.json"},"ai":{"faq":[{"question":"What is the continuous current rating of 3VA2010-7HN36-0AK0?","answer":"100 A continuous, and it holds that rating from 40 °C through 70 °C ambient without derating."},{"question":"Where can I buy 3VA2010-7HN36-0AK0?","answer":"Sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2010-7HN36-0AK0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2010-7HN36-0AK0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}